Yokogawa Data Logging Software GA10 User Manual
Page 36

3-12
IM 04L65B01-01EN
Tag Settings
Tag settings are used to set display groups and other
settings in a project. Therefore, even if you change the
device channel assigned to a tag, there is no need to
change display group settings or other settings that use
tags.
The tag settings are explained below.
(1) Collect (tag index)
These are unique tag numbers assigned
sequentially starting with 0001. You cannot change
the numbers. Click the boxes to specify whether to
enable data collection.
(2) Record
Click the boxes to specify whether to enable data
recording.
(3) Device
Specify the names of the devices to assign to the
tags.
(4) Channel
Specify the channels to assign to the tags. Clicking
a button displays a separate window. Select a
channel number to apply it to the sheet.
(5) Tag No. and Tag Comment
Enter aliases for the tags as tag numbers and tag
comments. Specify up to 16 characters for tag
numbers and 32 characters for tag comments.
You can select which name to display (Tag Index,
Tag No., or Tag Comment) to suit your purpose. To
select which name to display, on the
View menu,
click
Tag Display Form.
(6) Type
Specify the tag data types. Click the arrows, and
select from the following data types.
Data Type
Description
ANY
Any data type
BOOL
Boolean
SHORT
2-byte signed integer
USHORT
2-byte unsigned integer
LONG
4-byte signed integer
ULONG
4-byte unsigned integer
FLOAT
4-byte single-precision floating-point number
LOG (Old)
Data type for LOG input channels (DXAdvanced
series)
LOG
Data type for LOG input channels (FX1000 series)
Chapter 3 Configuring and Starting Data Collection and Recording
Refer to the following table for the data types of the
channels on data source devices.
Model
Channel Type
Data Type
DAQLOGGER
DAQ32Plus
MXLOGGER
All channels
LONG
GX/GP
Measurement channels
(excluding DI channels )
LONG
DI channels
BOOL
Excluding the above
Same as "Other"
Devices defined
using Modbus device
definition files
All channels
The type
specified in the
definition file
(FLOAT)
Other
Measurement channels SHORT
Math channel
LONG
Control channel
SHORT
Extra channel
SHORT
Math channel whose
input is LOG
LOG
(7) Dec. Point
Specify the number of decimal places for tags. Click
the arrows to select the number of digits (0 to 5).
Select the same setting as the decimal place setting
specified on the device. Specify ANY to retrieve the
decimal place information from the device at the
start of data collection.(See below.)
Type, Dec. Point, and ANY
GA10 can continue data collection even if you
change the connected device in the middle of
data collection as long as the Type and Dec. Point
settings are the same. For example, if you set
the tag Type to SHORT and change the device
to another type in the middle of data collection
(for maintenance or other purpose), as long as
the measurement channels use the same Type
and Dec. Points settings, you can continue data
collection.
Note that the tag Type (6) and Dec. Point (7) options
include a value called ANY.
You can select ANY if you want to retrieve the
channel information from the device at the start of
data collection and use those settings to perform
data collection. However, if the data collection time
is set to PC time and the device is not connected
within 3 seconds after the start of data collection, the
channel information will not be retrieved at the start
of data collection even if ANY is specified.
In this situation, the channel information that was
retrieved from the device at the time of device
registration is used. This is not a problem as long as
the channel information at the start of data collection
is the same as the channel information that was
retrieved from the device at the time of device
registration.
Using ANY makes the data type and decimal place
settings easier. However, you cannot verify the
actual data type.
Asked Questions (FAQ)”
Note
• If the data collection channel is LOG input, set the
data type to LOG. If set to LOG, the decimal place
setting is void.
• If the data type is set to BOOL, the decimal place
setting is void.