beautypg.com

App index – Yokogawa Value Series FX1000 User Manual

Page 95

background image

3-13

IM 04L21B01-17EN

Commands

1

2

3

4

5

6

App

Index

When Setting Channels to Square Root

Computation

Syntax

SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,
p11
p1 Measurement channel number
p2 Setting type (SQRT)
p3 Measuring range
p4 Span lower limit
p5 Span upper limit
p6 Scaling lower limit (–30000 to 30000)
p7 Scaling upper limit (–30000 to 30000)
p8 Scaling decimal place (0 to 4)
p9 Unit (up to 6 characters)
p10 Low-cut function (OFF, ON)
p11 Low-cut point (0 to 50)

Query

SR[p1]?

Example Convert the DC voltage measured on channel

001 to a flow amount using the square root
computation. Set the measuring range to 6 V, the
span lower limit to 1 V, the span upper limit to 5
V, the scaling lower limit to 10.0 m

3

/s, and the

scaling upper limit to 100.0 m

3

/s.

SR001,SQRT,6V,1000,5000,100,1000,1,
m3/s

Description • Set p1 and p3 by referring to the table in

section 3.3.

• For parameters p4 and p5, enter values with

five digits or less excluding the decimal point.

• For parameters p6, p7, and p8, either set all

three parameters, or omit all three parameters.

For 1-5V DC Voltage Input

Syntax

SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10

p1 Measurement channel number
p2 Input type (1-5V)
p3 Measuring range (1-5V)
p4 Span lower limit (800 to 5200)
p5 Span upper limit (800 to 5200)
p6 Scaling lower limit (–30000 to 30000)
p7 Scaling upper limit (–30000 to 30000)
p8 Scaling decimal place (0 to 4)
p9 Unit (up to 6 characters)
p10 Low-cut function (ON/OFF)

Query

SR[p1]?

Example Set the channel 005 input type to 1-5V, the span

lower limit to 1 V, the span upper limit to 5 V, and
turn on the 1-5V low-cut function.
SR005,1-5V,1-5V,1000,5000,,,,,ON

Description • Set p1 by referring to the table in section 3.3.

• For parameters p4 and p5, enter values with

four digits or less excluding the decimal point.

• For parameters p6, p7, and p8, either set all three

parameters, or omit all three parameters.

When Setting Channels to Log Scale (/LG1 option)

For details on “log input” and “log linear input/
pseudo log input”, see section 3.13 in the
FX1000 User’s Manual, IM 04L21B01-01EN.

• When Setting Channels to Log Input

Syntax

SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10

p1 Measurement channel number
p2 Setting type (LogT1)
p3 Measuring range (20MV, 60MV, 200MV, 1V,

2V, 6V, 20V, 50V)

p4 Span lower limit
p5 Span upper limit
p6 Mantissa of the scaling lower limit (100 to

999)

p7 Exponent of the scaling lower limit (–15 to

15)

p8 Mantissa of the scaling upper limit (100 to

999)

p9 Exponent of the scaling upper limit (–15 to

15)

p10 Unit (up to 6 characters)

Query

SR[p1]?

Example Execute a logarithmic scaling computation on

the DC voltage measured by channel 001, and
output the result. Set the measuring range to 6 V,
the span lower limit to 1 V, the span upper limit
to 5 V, the scaling lower limit to 1.00E+01, the
scaling upper limit to 1.00E+04, and the unit to
Unit1.
SR001,LogT1,6V,1000,5000,100,1,100,
4,Unit1

Description • Set the parameters so that p4 is less than p5.

• The settable scaling range is 1.00E–15 to

1.00E+15.

• Use three digits to set p6 and p8. “100” means

“1.00.”

• Set the parameters so that p7 is less than p9.
• Set the parameters so that “p9 – p7” conforms

to the following conditions:
• The maximum value is 15.
• When p6 is 100, the minimum value is 1.
• When p6 is a value other than 100, the

minimum value is 2.

3.4 Setting Commands