beautypg.com

11 usage example of the modbus function, 11 usage example of the modbus function -49, App index – Yokogawa Value Series FX1000 User Manual

Page 57: System configuration and actions

background image

1-49

IM 04L21B01-17EN

Using the Ethernet Interface (/C7 Option)

1

2

3

4

5

6

App

Index

1.11 Usage Example of the Modbus Function

Explains the setting example for both Modbus client and server on FX1000s connected
via the Ethernet. In this section, the FX that has been set as the Modbus server is
referred to as “FX1000 server.” FXs that have been set as Modbus clients are each
referred to as “FX1000 client.”

System Configuration and Actions

Uses the measurement channel, computation channel, and communication input data as
described in the figure below. Assumes other conditions are set properly.

FX1000 Server

(Modbus server)

Ethernet

Measured data

Command

Reads the FX’s measured data,

and uses a computation channel

(/M1, /PM1, and /PWR1 options) to display it.

FX1000 Client

(

Modbus

client)

Measurement channel 001

Input range: –2.0000 to 2.0000 V

Computation channel 101

–2.0000 to 2.0000V

Communication input data C01

Modbus service port

502 (by default)

Start the computation.

Display the channel on Group 1

Server number: 1

Action

• The

FX1000 client reads the measured value of channel 001 on the FX1000 server

into the communication input data C01. C01 is displayed on a computation channel
101 by including the data in the equation. The computation channel 101 is assigned to
Group1.

• The measured value of channel 001 on the

FX1000 server is transferred to the

FX1000 client as an integer in the range of –20000 to 20000.

• The

FX1000 client displays the read data as –2.0000 to 2.0000 V using the

computation channel 101. The following conversion is applied.

Value on the computation channel 101 of the FX1000 client
= Communication input data C01 x 0.0001