5 control commands, 5 control commands -30, Bt sets a batch name – Yokogawa Value Series FX1000 User Manual
Page 112: Bu sets a batch comment, Ud switches the screen, Ps starts or stops recording, Ak clears alarm output (acknowledges alarms)
3-30
IM 04L21B01-17EN
3.5 Control Commands
BT
Sets a batch name
Syntax
BT p1,p2,p3
p1 Fixed to 1
p2 Batch number (up to 32 characters)
p3 Lot number (up to 8 digits)
Query
BT[p1]?
Example Set the batch name structure to have the batch
number “PRESS5LINE” and the lot number 007.
BT1,PRESS5LINE,007
Description Set p1 by referring to the table in section 3.3.
BU
Sets a batch comment
Syntax
BU p1,p2,p3
p1 Fixed to 1
p2 Comment number (1 to 3)
p3 Comment string (up to 50 characters)
Query
BU[p1[,p2]]?
Example Set comment number 2 to “THIS_PRODUCT_
IS_COMPLETED.”
BU1,2,THIS_PRODUCT_IS_COMPLETED
Description Set p1 by referring to the table in section 3.3.
UD
Switches the screen
To return to the screen that was in use before you
started using communication commands
Syntax
UD p1
p1 Screen type (0)
Example Return to the screen that was in use before you
started using communication commands.
UD0
To switch between displays
Syntax
UD p1,p2,p3
p1 Screen type (1)
p2 Display item
TREND Trend display
DIGITAL Digital display
BAR
Bar graph display
OVERVIEW Overview display
(alarm indicator)
ALARM Alarm summary display
MESSAGE Message summary display
MEMORY Memory summary display
MODBUS-M Modbus master status display
MODBUS-C Modbus client status display
RELAY Relay status display
REPORT Report display
HISTRICAL Historical trend display
COLUMN_BAR
Stacked bar graph
p3 Display group number
Example Switch to the trend display, and select display
group number 4.
UD1,TREND,4
Description • The setting p2 = MODBUS-M is only valid
if the serial interface protocol is set to
MODBUS-M.
• The settings p2 = REPORT and p2 =
COLUMN_BAR are only valid on models with
the /M1, /PM1, or /PWR1 math option.
• The setting p2 = MODBUS-C is only valid
on models with the Ethernet interface (/C7
option).
• Set p3 by referring to the table in section 3.3.
To switch the operation screen
Syntax
UD p1,p2,p3,p4,p5,p6,p7
p1 Screen type (4)
p2 Automatic display switching (ON, OFF)
p3 Switches between all channel display and
group display (ALL, GROUP)
p4 Scale display (ON, OFF)
p5 Digital display (ON, OFF)
p6 Message display options
1
Normal display
2
List display
p7 Trend space (ON, OFF)
Example Turn on automatic display switching, switch to
the group display, turn on the scale display, and
turn off the digital display.
UD4,ON,GROUP,ON,OFF
Description • Parameter p2 is valid for the trend, digital, and
bar graph displays. Use the SE command to
set the switching interval.
• Parameters p3 to p7 are valid for the trend
display.
PS
Starts or stops recording
Syntax
PS p1
p1 Starts or stops recording
0
Start
1
Stop
Example Start recording.
PS0
Description When you start recording, the FX records
display, event, and report data to the internal
memory.
AK
Clears alarm output
(acknowledges alarms)
Syntax
AK p1
p1 Executes alarm acknowledgement
0
Alarm acknowledge
Example Clear the alarm output (acknowledge alarms).
AK0
3.5 Control Commands