Wo sets alarm and do settings, Wh sets alarm hysteresis – Yokogawa Value Series FX1000 User Manual
Page 118
3-36
IM 04L21B01-17EN
Detailed POP3 settings
Syntax
WU p1,p2,p3
p1 Setting type (POP3)
p2 Delay after accessing POP3 until
transmission (in seconds; 0 to 10)
p3 POP3 login method (PLAIN, APOP)
Description On models that have the Ethernet interface (/C7
option), you can set p1 to POP3.
Detailed FTP server settings
Syntax
WU p1,p2
p1 Setting type (FTPSERVER)
p2 Directory output format (MS-DOS, UNIX)
MS-DOS
UNIX
Description On models that have the Ethernet interface (/C7
option), you can set p1 to FTPSERVER.
Query
WU[p1]?
Example This is an example for general environment
settings. Display tags and use English as the
display language.
WUGENERAL,TAG,ENGLISH
WO
Sets alarm and DO settings
Alarm and DO settings
Syntax
WO p1,p2,p3,p4,p5
p1 Alarm setting (ALARM)
p2 Reflash operation (OFF, ON)
p3 Interval for the low limit on the rate-of-
change (1 to 32)
p4 Interval for the high limit on the rate-of-
change (1 to 32)
p5 Holding of the alarm status display
HOLD
NONHOLD
Internal switch settings
Syntax
WO p1,p2
p1 DO type (SWITCH)
p2 AND switch number
NONE
No AND setting
S01
Only specify S01
S01-Sxx Specify S01 to Sxx
xx = 02 to 30
Output relay settings
Syntax
WO p1,p2,p3,p4,p5
p1 DO type (RLY)
p2 Relay number
NONE
No AND setting
I01
Only specify I01
I01-Ixx Specify I01 to Ixx
xx = 02 to 06 and 11 to 16
p3 Energize or de-energize the relay
DE_ENERGIZE
ENERGIZE
p4 Holding of the relay
NONHOLD
HOLD
p5 Relay action on ACK
NORMAL
RESET
Query
WO[p1]?
Example Specify no AND operation of the output relays,
set the relay action to energize, and release
the relay output when the ACK operation is
performed regardless of the alarm status.
WORLY,NONE,ENERGIZE,HOLD,RESET
WH
Sets alarm hysteresis
Measurement channels
Syntax
WH p1,p2,p3
p1 Channel type (MEASURE)
p2 Hysteresis on high and low limit alarms
(0 to 50)
p3 Hysteresis on difference high and low limit
alarms (0 to 50)
Computation channels
Syntax
WH p1,p2
p1 Channel type (MATH)
p2 Hysteresis on high and low limit alarms
(0 to 50)
Query
WH[p1]?
Example For measurement channels, set the high and low
limit alarm hysteresis to 4.0% and the difference
high and low limit alarm hysteresis to 0.0%.
WHMEASURE,40,0
Description • You can set computation channels on models
with the /M1, /PM1, or /PWR1 math option.
• The hysteresis of any channels that are set to
Log scale (/LG1 option) is fixed to 0.
3.6 Basic Setting Commands