beautypg.com

Yokogawa Value Series FX1000 User Manual

Page 78

background image

2-14

IM 04L21B01-17EN

• Communication conditions

The read cycle, Inter-block delay, Time out, Auto recovery, and Retrials settings are

displayed.

• Communication Status

The communication status is displayed using the status lamp and the detail code.

Status Lamp

Detail Code

Meaning

Green

Good

Communication is operating normally.

Yellow

Command is readying.

Red

Communication is stopped.

Common to yellow

None

No response from the slave device.

and red

Func

The slave device cannot execute the command

from the FX.

Regi

The slave device does not have the specified

register.

Err

The response data from the slave device is broken

(communication error).

(Space)

The detail code is not displayed until the status is

confirmed when communication is started.

Resuming Command Transmission

You can use the front panel keys to resume command transmission to a slave device to
which communication is stopped (red status lamp).

1.

Using the up and down arrow keys, select the command corresponding to the

slave device to which transmission will be resumed. The message “Push [right
arrow] key to refresh” appears.

2.

Press the right arrow key. The FX starts command transmission to the specified

slave.

Data When Communication Is Stopped and during Connection Retrials

For Modbus master, the communication input data is held at the previous values while
the command is being retried.
If the command transmission stops such as due to a connection drop, the status turns
red, and the communication input data will be error data. On communication channels,
“+OVER” or –OVER is displayed according to the FX settings.

Data Dropout

Data drop occurs when the commands from 1 to 16 do not complete within the read
cycle (see appendix 1). When a data dropout occurs, the communication input data is
held at the previous value. A message indicating the data dropout is also displayed on
the Modbus status display. If this happens, take measures such as making the read cycle
longer or reducing the number of commands. Confirm that no data dropout occurs on the
modbus status log screen.

2.6 Using Modbus to Read Data From and Write Data to Other Devices