App index, Xg sets the time zone, Xn sets the date format – Yokogawa Value Series FX1000 User Manual
Page 121: Yb sets host information (/c7 option)
3-39
IM 04L21B01-17EN
Commands
1
2
3
4
5
6
App
Index
RM
Sets a report channel (/M1, /PM1,
and /PWR1 options)
When you are not using report channels
Syntax
RM p1,p2
p1 Report channel number
p2 Report channel usage (OFF)
Query
RM[p1]?
Example Disable the channel 001 report channel.
RM001,OFF
Description Set p1 by referring to the table in section 3.3.
When you are using report channels
Syntax
RM p1,p2,p3,p4
p1 Report channel number
p2 Report channel usage (ON)
p3 Number of the measurement or computation
channel on which to report
p4 Conversion of the unit of time for integration
OFF
Values are not converted.
/S
Values are converted as though
the physical values are integrated
in units of seconds.
/MIN
Values are converted as though
the physical values are integrated
in units of minutes.
/H
Values are converted as though
the physical values are integrated
in units of hours.
/DAY
Values are converted as though
the physical values are integrated
in units of days.
Query
RM[p1]?
Example Use report channel number R01. Set the
number of the channel on which to report to 001
and convert the unit of time for integration to
seconds.
RM001,ON,001,/S
Description • You can use this command on models with the
/M1, /PM1, or /PWR1 math option.
• Set p1 and p3 by referring to the table in
section 3.3. Errors are returned for any reports
for channels that are set to Log scale (/LG1
option).
• About parameter p4
Because the FX integrates sampled data
over each scan interval, the physical value
measured over a given unit of time may be
different from the actual integrated value
(because the unit of time is different from the
scan interval). If this occurs, set p4 to the
same unit of time as that which is being used
for the physical value that you are measuring.
The FX calculates the integrated value using
one of the following conversion formulas
based on the parameter.
OFF
Σ(measured value)
/S
Σ(measured value) × scan interval
/MIN
Σ(measured value) × scan
interval/60
/HOUR Σ(measured value) × scan
interval/3600
/DAY
Σ(measured value) × scan
interval/86400
The scan interval unit is seconds.
XG
Sets the time zone
Syntax
XG p1,p2
p1 Time offset from GMT (–1300 to 1300)
First two digits: Hour (00 to 13)
Second two digits: Minute (00 to 59)
p2 Time deviation limit at which the function
that gradually adjusts the time is enabled
(OFF, 10S, 20S, 30S, 1MIN, 2MIN, 3MIN,
4MIN, 5MIN)
Example Set the time offset to 9 hours ahead of GMT and
the deviation limit to 30 seconds.
XG0900,30S
XN
Sets the date format
Syntax
XN p1
p1 Date format (Y/M/D, M/D/Y, D/M/Y, D.M.Y)
Query
XN?
Example Set the date format to year/month/day.
XNY/M/D
YB
Sets host information (/C7
option)
Syntax
YB p1,p2
p1 Host name (up to 64 characters)
p2 Domain name (up to 64 characters)
Query
YB?
Example Set the host name to “fx1000” and the domain
name to “fxadv.recorder.com.”
YBfx1000,fxadv.recorder.com
3.6 Basic Setting Commands