Yokogawa Value Series FX1000 User Manual
Page 52
1-44
IM 04L21B01-17EN
• Unit
Select
Auto if the unit number of the destination server is not required; Otherwise,
select
Fixed. If you select Fixed, the unit number item is displayed.
• No.
Enter a fixed unit number in the range of 0 to 255.
Setting the transmitted commands
• Client command number
Select 1 to 16 for the transmitted command numbers to be configured.
• Command type
Set the command type to Off, R-M, W, or W-M. If you select a command type
other than
Off, the client channel, server number, register, and data type items are
displayed.
R-M: Read to the communication input data (32-bit floating point type) from the
server.
W:
Write the measurement channel (16-bit signed integer type) to the server.
W-M: Write the computation channel (32-bit signed integer type) to the server.
You can only select
R-M and W-M on models that have the /M1, /PM1, or /PWR1 math
option.
• First/Last (client channels)
Enter the first and last channel numbers for I/O. The range of channels that you can
enter varies depending on the command type as follows:
R-M: C01 to C24, W: 001 to 012, W-M: 101 to 124
• Server (server number)
Select the server number from 1 to 16.
• Regi. (registers on the server)
Set the register number of the server.
For an input register, select in the range of 30001 to 39999 and 300001 to 365536.
For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.
The register numbers you can specify vary depending on the command type. See
section 6.3.
Specifying the Register Number
Specify the register number on the FX by using the “reference number” (such as
the number 40001 written above). For example, for the YOKOGAWA UT35A digital
indicating controller, the D register number corresponds to the reference number as
shown in the following table.
D-Reg. No.
Ref. No.
D2001
42001
For a server device that calls the register using a “relative number,” add 30001,
300001, 40001, or 400001 to obtain a reference number.
Register Type Relative Number
Reference Number
Expression
Hold register
1004
41005
1004 + 40001
14567
414568
14567 + 400001
Input register
0000
30001
0000 + 30001
• Type
Data type.
Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT32_L, FLOAT_B, or
FLOAT_L.
The data type you can specify vary depending on the command type. See section 6.3.
1.10 Using Modbus to Read Data From and Write Data to Other Devices