3-25

IM 04L21B01-17EN

Commands

1

2

3

4

5

6

App

Index

TX

Sets the ancillary operation of

the start key (/M1,/PM1, and

/PWR1 options)

Syntax

TX p1
p1 Computation operation (OFF, START,

RESET+START)

Query

TX?

Example Configure the start key so that computation also

begins when the start key is pressed.
TXSTART

BH

Sets a batch text field

Syntax

BH p1,p2,p3,p4
p1 Fixed to 1
p2 Field number (1 to 8)
p3 Field title (up to 20 characters)
p4 Field string (up to 30 characters)

Query

BH[p1[,p2]]?

Example Set the field title to “OPERATOR” and the field

string to “123-01” for field number 2.
BH1,2,OPERATOR,123-01

Description For the characters that you can use, see

appendix 3.

EH

Sets calibration correction (/CC1

option)

You cannot specify calibration correction for a
channel whose log scale (/LG1 option) mode is
set to LogType2.

When p2 is set to BEGIN

Syntax

EH p1,p2,p3
p1 Measurement channel number
p2 Type of operation (BEGIN)
p3 Number of break points of the calibration

segment (OFF, 2 to 16)
OFF

Turns calibration off

2 to 16 Number of break points

When p2 is set to SET

Syntax

EH p1,p2,p3,p4,p5
p1 Measurement channel number
p2 Type of operation (SET)
p3 A specific break point (1 to 16)
p4 Input value of the specific break point
p5 Output value of the specific break point

Description • Set p1 by referring to the table in section 3.3.

• The range of p4 and p5 varies depending on

the currently specified range.

• When the measurement range is set to scale,

the range of p4 and p5 is –30000 to 30000.

• Set input value p4 so that the value increases

as break point p3 increases.

When p2 is set to END

Syntax

EH p1,p2
p1 Measurement channel number
p2 Type of operation (END)

Example Set three break points on channel 002.

EH002,BEGIN,3
EH002,SET,1,0,1
EH002,SET,2,50,49
EH002,SET,3,100,101
EH002,END

Description • First, send the command with p2 set to BEGIN

to specify the number of break points.

• Then, send this command with p2 set to SET

as many times as is necessary to specify the
values of each break point.

• Finally, send this command with p2 set to END

to finalize the settings.

• Send the command “

EH2?” to have the FX

return the channel 002 settings.

• The FX returns the settings in the format

shown in the above example.

BD

Sets an alarm delay

Syntax

BD p1,p2
p1 Measurement or computation channel

number

p2 Alarm delay (1 to 3600)

Query

BD[p1]?

Example Set the channel 001 alarm delay to 120 seconds.

BD001,120

Description • Set p1 by referring to the table in section 3.3.

• The p2 unit is seconds.

NP

Sets the VT ratio, CT ratio, and

low-cut power (/PWR1 option)

You cannot use this command to configure
settings while recording (memory sampling) or
computation is in progress.

Setting the VT ratio and CT ratio

Syntax

NP p1,p2,p3,p4
p1 Setting type (VTCT)
p2 VT ratio (10 to 60000)
p3 CT ratio decimal place (0 to 2)
p4 CT ratio value

Query

NP[p1[,p2]]?

Example Set the VT ratio to 10.0 and the CT ratio to

123.45.
NPVTCT,100,2,12345

3.4 Setting Commands