App index, Bh sets a batch text field, Eh sets calibration correction (/cc1 option) – Yokogawa Value Series FX1000 User Manual
Page 107: Bd sets an alarm delay
3-25
IM 04L21B01-17EN
Commands
1
2
3
4
5
6
App
Index
TX
Sets the ancillary operation of
the start key (/M1,/PM1, and
/PWR1 options)
Syntax
TX p1
p1 Computation operation (OFF, START,
RESET+START)
Query
TX?
Example Configure the start key so that computation also
begins when the start key is pressed.
TXSTART
BH
Sets a batch text field
Syntax
BH p1,p2,p3,p4
p1 Fixed to 1
p2 Field number (1 to 8)
p3 Field title (up to 20 characters)
p4 Field string (up to 30 characters)
Query
BH[p1[,p2]]?
Example Set the field title to “OPERATOR” and the field
string to “123-01” for field number 2.
BH1,2,OPERATOR,123-01
Description For the characters that you can use, see
appendix 3.
EH
Sets calibration correction (/CC1
option)
You cannot specify calibration correction for a
channel whose log scale (/LG1 option) mode is
set to LogType2.
When p2 is set to BEGIN
Syntax
EH p1,p2,p3
p1 Measurement channel number
p2 Type of operation (BEGIN)
p3 Number of break points of the calibration
segment (OFF, 2 to 16)
OFF
Turns calibration off
2 to 16 Number of break points
When p2 is set to SET
Syntax
EH p1,p2,p3,p4,p5
p1 Measurement channel number
p2 Type of operation (SET)
p3 A specific break point (1 to 16)
p4 Input value of the specific break point
p5 Output value of the specific break point
Description • Set p1 by referring to the table in section 3.3.
• The range of p4 and p5 varies depending on
the currently specified range.
• When the measurement range is set to scale,
the range of p4 and p5 is –30000 to 30000.
• Set input value p4 so that the value increases
as break point p3 increases.
When p2 is set to END
Syntax
EH p1,p2
p1 Measurement channel number
p2 Type of operation (END)
Example Set three break points on channel 002.
EH002,BEGIN,3
EH002,SET,1,0,1
EH002,SET,2,50,49
EH002,SET,3,100,101
EH002,END
Description • First, send the command with p2 set to BEGIN
to specify the number of break points.
• Then, send this command with p2 set to SET
as many times as is necessary to specify the
values of each break point.
• Finally, send this command with p2 set to END
to finalize the settings.
• Send the command “
EH2?” to have the FX
return the channel 002 settings.
• The FX returns the settings in the format
shown in the above example.
BD
Sets an alarm delay
Syntax
BD p1,p2
p1 Measurement or computation channel
number
p2 Alarm delay (1 to 3600)
Query
BD[p1]?
Example Set the channel 001 alarm delay to 120 seconds.
BD001,120
Description • Set p1 by referring to the table in section 3.3.
• The p2 unit is seconds.
NP
Sets the VT ratio, CT ratio, and
low-cut power (/PWR1 option)
You cannot use this command to configure
settings while recording (memory sampling) or
computation is in progress.
Setting the VT ratio and CT ratio
Syntax
NP p1,p2,p3,p4
p1 Setting type (VTCT)
p2 VT ratio (10 to 60000)
p3 CT ratio decimal place (0 to 2)
p4 CT ratio value
Query
NP[p1[,p2]]?
Example Set the VT ratio to 10.0 and the CT ratio to
123.45.
NPVTCT,100,2,12345
3.4 Setting Commands