App index configured alarm information data, Manual sampled data, Report data – Yokogawa Value Series FX1000 User Manual
Page 169
4-33
IM 04L21B01-17EN
Responses
1
2
3
4
5
6
App
Index
Configured Alarm Information Data
• The FE6 command is used to output the data.
• The ID number of the output format is 26.
• You can use the CB command to specify whether to output the data of measurement
channels set to skip and computation channels set to OFF.
• The figure below indicates the format.
Number of blocks
Block size
Configured alarm information block 1
• • •
Configured alarm information block n
(Reserved) (Reserved)
2 bytes
1 byte
1 byte
1 byte
1 byte
Version (Reserved)
2 bytes
Format Details
Item
Description
Output Value
Version
Format version
2
Number of blocks
1
Number of configured alarm information blocks
Up to 36
Block size
1
Size of the of configured alarm information blocks
32
Block 1 to n
Configured alarm information blocks
Up to 1152 bytes
See Block Details.
1: Output in the byte order specified by the BO command.
Block Details
Each value is the corresponding setting on the FX, but with the decimal point
removed. For example, “120” corresponds to a setting of “1.20” on the FX.
Item
Number
of Bytes Notes
Channel number
1
2
1 to 124
Decimal place
1
0 to 4
When you are using a channel that is set to Log scale,
2
the decimal place of the
FX digital display’s mantissa is displayed.
(Reserved)
1
0
Alarm type
4
The following settings are entered in order from level 1 to 4.
0: Setting off, 1: H (high limit), 2: L (low limit), 3: h (difference high limit),
4: l (difference low limit), 5: R (high limit on rate-of-change),
6: r (low limit on rate-of-change), 7: T (delay high limit), 8: t (delay low limit)
Alarm value
1
4x4
The alarm values are entered in order from level 1 to level 4.
When the Log scale
2
is not used: Alarm setting on the FX
When the Log scale
2
is used: The same value as the mantissa of the alarm setting
on the FX
Alarm value
(exponent)
1x4
The alarm values are entered in order from level 1 to level 4.
When the Log scale
2
is not used: 0
When the Log scale
2
is used: Same value as the exponent of the FX alarm setting
(Reserved)
4
0
1
Output in the byte order specified by the BO command.
2
/LG1 option
Manual Sampled Data
• The ME or MO command is used to output the data.
• The ID number of the output format is 17. See section 4.1.
• For the data format, see the FX1000 User’s Manual, IM 04L21B01-01EN.
Report Data
• The ME or MO command is used to output the data.
• The ID number of the output format is 18. See section 4.1.
• For the data format, see the FX1000 User’s Manual, IM 04L21B01-01EN.
4.3 Output Format of Binary Data