beautypg.com

App index – Yokogawa Value Series FX1000 User Manual

Page 183

background image

6-9

IM 04L21B01-17EN

Specifications

1

2

3

4

5

6

App

Index

Hold Register (shared with the Modbus slave function)

• Common Items

• The client device can read and write to the hold registers.
• Communication input data is an option (/M1, /PM1, or /PWR1).

• Reading from and Writing to Communication Input Channels

Communication input data can be handled on a computation channel by including the

data in the equation of a FX computation channel.

Hold Register Data

Data Type

400001

Communication input data C01

16-bit signed integer

|

|

400024

Communication input data C24

• Precautions to be taken when the client device reads the data

The communication input data of the FX is floating point type, but the data is converted to

signed 16-bit integer when the data is read.

• Precautions to be taken when the client device writes the data

Only data in signed 16-bit integer type can be written. Floating point values cannot be

written.
400601

Lower bytes of communication input data C01

32-bit floating point

400602

Higher bytes of communication input data C01

|

|

400647

Lower bytes of communication input data C24

400648

Higher bytes of communication input data C24

• Precautions to be taken when the client device writes the data

Input range: –9.9999E29 to –1E–30, 0, 1E–30 to 9.9999E29

If values outside this range are used on a computation channel, a computation error

occurs.
400301

Lower bytes of communication input data C01

32-bit signed integer

400302

Higher bytes of communication input data C01

|

|

400347

Lower bytes of communication input data C24

400348

Higher bytes of communication input data C24

• Note when a client device reads data

The FX communication input data is floating-point, but when it is read, it is converted to 32-

bit signed integer.

• Note when a client device writes data

Data can only be written in 32-bit signed integer. Floating-point values cannot be written.

• Operating Devices

You can use the following hold registers.

You can perform a portion of the operations

by writing in the registers.
• Internal switch
• Lot number
• Batch number
• Recording (memory sampling) start and stop
• Alarm ACK
• Computation start, computation stop, computation reset, computation dropout ACK
• Manual sampling, event data sampling start trigger, and snapshot
• Message and free message writing

6.3 Modbus Protocol Specifications