beautypg.com

Modbus server function, Modbus server specifications – Yokogawa Value Series FX1000 User Manual

Page 180

background image

6-6

IM 04L21B01-17EN

Modbus Server Function

Modbus Server Specifications

Communicate via ModbusTCP
Communication media: Ethernet 10Base-T
Port:

502/tcp (default value)

Command wait timeout: 1 minute. However, the timeout to receive the command after

starting to receive the command is 10 seconds.

Maximum number of connections:

2

Supported functions:

The functions that the FX supports are listed below.

Function

Code

Function

Operation

3

Read the hold register (4XXXXX) The client device reads the FX’s communication input

data.

4

Read the input register

(3XXXXX)

The client device reads the computed, measured,

alarm, and time data of the FX.

6

Single write to hold register

(4XXXXX)

The client device writes to the communication input

data of the FX.

8

Loopback test

The client device performs a loopback test of the FX.

16

Write to the hold register

(4XXXXX)

The master device writes to the communication input

data of the FX.

Register assignments (shared with the Modbus slave function)

Measurement ch.

Computation ch.

Measurement ch.

Computation ch.

Time

Measured data

Alarm status

Computed data

Alarm status

Alarm list

Alarm list

Type

16-bit signed integer

Bit string

32-bit signed integer

Bit string

Bit string

Bit string

16-bit signed integer

Number

300001 to 300012

301001 to 301012

302001 to 302048

303001 to 303024

306001 to 306003

306021 to 306026

309001 to 309008

Kind

Input register

Communication input data

Data type

16-bit signed integer

32-bit floating point

Number

400001 to 400024

400301 to 400348

See “Operating Devices” under “Hold Register.”

Kind

Hold register

Client

Read

Client

Read

Write

Operating devices

6.3 Modbus Protocol Specifications