Checking the Modbus Operating Status
Displaying the Modbus Operating Status
◊ Press
DISP/ENTER and select INFORMATION > MODBUS CLIENT.
Note
To display
MODBUS CLIENT on the screen selection menu, you need to change the setting
using the menu customize function. The operation is as follows:
◊ Press
MENU
(to switch to setting mode), and select the
Menu
tab >
Menu customize
>
Display menu
1.
Select
INFORMATION > MODBUS CLIENT
2.
Press the
View soft key.
Host name or IP address of the server device
Register number
FX channels
Detail code
Status lamp
Communication condition
Cursor to select a command
(Used when resuming command transmission
to a server device using the front panel keys)
• Communication Conditions
The Read cycle and Connect.retry settings are displayed.
• Communication Status
The communication status is displayed using the status lamp and the detail code.
Status Lamp
Detail Code
Meaning
Green
Good
Communication is operating normally.
Yellow
Command is readying.
Orange
Trying to establish a TCP connection.
Red
Communication is stopped.
Common to yellow,
orange, and red
None
No response from the server device.
Func
The server device cannot execute the command from
the FX.
Regi
The server device does not have the specified register.
Err
There is an error in the response data from the server
device.
Link
Ethernet cable is disconnected.
Host
Unable to resolve the IP address from the host name.
Cnct
Failed to connect to the server.
Send
Failed to transmit the command.
BRKN
Failed to receive the response data or detected a
disconnection.
(Space)
The detail code is not displayed until the status is
confirmed when communication is started.
1.10 Using Modbus to Read Data From and Write Data to Other Devices