beautypg.com

App index checking the modbus operating status – Yokogawa Value Series FX1000 User Manual

Page 55

background image

1-47

IM 04L21B01-17EN

Using the Ethernet Interface (/C7 Option)

1

2

3

4

5

6

App

Index

Checking the Modbus Operating Status

Displaying the Modbus Operating Status

◊ Press

DISP/ENTER and select INFORMATION > MODBUS CLIENT.

Note

To display

MODBUS CLIENT on the screen selection menu, you need to change the setting

using the menu customize function. The operation is as follows:
◊ Press

MENU

(to switch to setting mode), and select the

Menu

tab >

Menu customize

>

Display menu

1.

Select

INFORMATION > MODBUS CLIENT

2.

Press the

View soft key.

Host name or IP address of the server device

Register number

FX channels

Detail code

Status lamp

Communication condition

Cursor to select a command

(Used when resuming command transmission

to a server device using the front panel keys)

• Communication Conditions

The Read cycle and Connect.retry settings are displayed.

• Communication Status

The communication status is displayed using the status lamp and the detail code.

Status Lamp

Detail Code

Meaning

Green

Good

Communication is operating normally.

Yellow

Command is readying.

Orange

Trying to establish a TCP connection.

Red

Communication is stopped.

Common to yellow,

orange, and red

None

No response from the server device.

Func

The server device cannot execute the command from

the FX.

Regi

The server device does not have the specified register.

Err

There is an error in the response data from the server

device.

Link

Ethernet cable is disconnected.

Host

Unable to resolve the IP address from the host name.

Cnct

Failed to connect to the server.

Send

Failed to transmit the command.

BRKN

Failed to receive the response data or detected a

disconnection.

(Space)

The detail code is not displayed until the status is

confirmed when communication is started.

1.10 Using Modbus to Read Data From and Write Data to Other Devices