App index, Xv sets the scan interval and a/d integration time, Xb sets burnout detection – Yokogawa Value Series FX1000 User Manual
Page 119: Xj sets rjc, Rf sets the key lock
3-37
IM 04L21B01-17EN
Commands
1
2
3
4
5
6
App
Index
XV
Sets the scan interval and A/D
integration time
Syntax
XV p1,p2,p3,p4
p1 Fixed to 1
p2 NORMAL Fixed
p3 Scan interval (125MS, 250MS, 1S, 2S, 5S)
p4 A/D integration time (AUTO, 50Hz, 60Hz,
100ms)
Query
XV[p1]?
Example Set the scan interval to 1 second.
XV1,NORMAL,1S
Description The selectable scan intervals vary depending on
the model. See the FX1000 User’s Manual, IM
04L21B01-01EN. You can only set p4 to 100ms
when p3 is set to 2S or 5S.
XB
Sets burnout detection
Syntax
XB p1,p2
p1 Measurement channel number
p2 Burnout processing
OFF
No processing
UP
Sets the measured result to
positive overflow
DOWN
Sets the measured result to
negative overflow
Query
XB[p1]?
Example Set the measured result to UP (positive overflow)
when a burnout is detected on channel 001.
XB001,UP
Description Set p1 by referring to the table in section 3.3.
XJ
Sets RJC
When using the internal compensation circuit
Syntax
XJ p1,p2
p1 Measurement channel number
p2 RJC mode (INTERNAL)
Query
XJ[p1]?
Example Set the channel 001 RJC to internal
compensation circuit.
XJ001,INTERNAL
When using an external RJC
Syntax
XJ p1,p2,p3
p1 Measurement channel number
p2 RJC mode (EXTERNAL)
p3 External RJC value (–20000 to 20000)
Query
XJ[p1]?
Example Set the channel 002 RJC to external, and set the
compensation value to 0 μV.
XJ002,EXTERNAL,0
Description • Set p1 by referring to the table in section 3.3.
• The p3 unit is μV.
XM
Sets the memory sampling
condition
Syntax
XM p1
p1 Data type
DISPLAY Display data
EVENT Event data
E+D
Display data and event data
Query
XM?
Example Set the memory sampling condition to display
data.
XMDISPLAY
Description You cannot specify E+D when:
• Trend interval switching is on.
RF
Sets the key lock
When p1 is set to KEY
Syntax
RF p1,p2,p3,p4,p5,p6
p1 Type (KEY)
p2 START key (FREE, LOCK)
p3 STOP key (FREE, LOCK)
p4 MENU key (FREE, LOCK)
p5 USER key (FREE, LOCK)
p6 DISP/ENTER key (FREE, LOCK)
When p1 is set to FUNC (function key)
Syntax
RF p1,p2,p3,p4,p5,p6,p7,p8
p1 Type (FUNC)
p2 Alarm ACK (FREE, LOCK)
p3 Message and batch (FREE, LOCK)
p4 Computation (FREE, LOCK)
p5 Data save (FREE, LOCK)
p6 E-mail and FTP (FREE, LOCK)
p7 Time operations (FREE, LOCK)
p8 Display operations (FREE, LOCK)
Description Even on models that do not have the Ethernet
interface (/C7 option), if you set p1 to FUNC, you
can specify a value for parameter p6 (the E-mail
and FTP setting), but it will be ignored.
When p1 is set to MEDIA (external storage media)
Syntax
RF p1,p2,p3
p1 Type (MEDIA)
p2 External storage media operations (FREE,
LOCK)
p3 Setting load operations (FREE, LOCK)
Description You cannot use this command with p1 set to
MEDIA on models that do not have a CF card
slot or USB interface (/USB1 option).
Query
RF[p1]?
Example Only lock the MENU key.
RFKEY,FREE,FREE,LOCK,FREE,FREE,FREE
3.6 Basic Setting Commands