beautypg.com

7 usage example of the modbus function, 7 usage example of the modbus function -15, App index – Yokogawa Value Series FX1000 User Manual

Page 79: System configuration and actions

background image

2-15

IM 04L21B01-17EN

Using the Serial Communication Interface (/C2 and /C3 Options)

1

2

3

4

5

6

App

Index

2.7 Usage Example of the Modbus Function

Explains the setting example for both Modbus master and slave on FX1000s connected
via the serial communication.

In this section, the FX that has been set as the Modbus

master is referred to as “FX1000 master.” FXs that have been set as Modbus slaves are
each referred to as “FX1000 slave.”

System Configuration and Actions

Uses the measurement channel, computation channel, and communication input data as
described in the figure below. Assumes other conditions are set properly.

FX1000 slave

(Modbus slave)

Serial communication

Reads the FX1000’s measured data,

and uses a computation channel

(/M1, /PM1, and /PWR1 options) to display it.

FX1000 master

(

Modbus

master)

Measurement channel 001

Input range: –2.0000 to 2.0000 V

Computation channel 101

-2.0000 to 2.0000V

Communication input data C01

Address: 1

Start the computation

Display the channel on Group 1

Measured data

Command

Action

• The

FX1000 master reads the measured value of channel 001 on the FX1000 slave

into the communication input data C01. C01 is displayed on a computation channel
101 by including the data in the equation. The computation channel 101 is assigned to
Group1.

• The measured value of channel 001 on the

FX1000 slave is transferred to the FX1000

master as an integer in the range of –20000 to 20000.

• The

FX1000 master displays the read data as –2.0000 to 2.0000 V on the

computation channel 101. The following conversion is applied.

Value on the computation channel 101 of the FX master

= Communication input data C01 x 0.0001