E-mail Format
The formats of alarm e-mails, scheduled e-mails, system e-mails, report e-mails, and test
e-mails are given below. For details on the common display items, see “Common Display
Items for All Formats” in this section.
Alarm Notification E-mail Format
• Subject
Subject: [Alarm Summary]
• Syntax
header1CRLF
header2CRLF
CRLF
Alarm_summary.CRLF
hostCRLF
CRLF
CRLF
mo/dd_hh:mi:ssCRLF
ccc···c=ddd···dCRLF
····························
CRLF
Access_the_following_URL_in_order_to_look_at_a_screen.CRLF
http://host.domain/CRLF
CRLF
cc c···c Channel number or tag
(Up to 16 characters. Channels set to Skip or Off are not output. (For
the channel number, see section 3.3.)
l Alarm level (1 to 4)
q Alarm type (H, L, h, l, R, r, T, t)
H (high limit alarm), L (low limit alarm), h (difference high limit alarm),
l (difference low limit alarm), R (high limit on rate-of-change alarm),
r (low limit on rate-of-change alarm), T (delay high limit alarm),
t (delay low limit alarm)
aaa Alarm status (off or on)
ddd···d Measured/Computed value (up to 10 digits including the sign and
decimal point) + unit (up to 6 characters)
+OVER:
Positive overrange
-OVER:
Negative overrange
Burnout:
Burnout data
*****:
Error data
The FX transmits channel numbers, alarm types, and alarm statuses for up to 10
events in a single e-mail.
1.4 Sending E-mail Messages