beautypg.com

App index, Tu sets an event action – Yokogawa Value Series FX1000 User Manual

Page 105

background image

3-23

IM 04L21B01-17EN

Commands

1

2

3

4

5

6

App

Index

TU

Sets an event action

Syntax

TU p1,p2,p3,p4,p5,p6,p7
p1 Logic number (1 to 40)
p2 Event type

NONE
REMOTE

Remote control input

RELAY

Alarm output relay

SWITCH

Internal switch

ALARM

Alarm

TIMER

Timer

MATCHTIMETIMER Match time
USERKEY

USER key

p3 Event details

p2 = REMOTE

Remote number

p2 = RELAY

Relay number

p2 = SWITCH

Internal switch number

p2 = TIMER

Timer number

p2 = MATCHTIMETIMER

Match time timer
number

p2 = Any other value

Don’t care

p4 Action type

MEMORYSTART/STOP

Memory start or
memory stop

MEMORYSTART

Memory start

MEMORYSTOP

Memory stop

TRIGGER

Event trigger

ALARMACK

Alarm
acknowledgement

MATHSTART/STOP Starts or stops computation
MATHSTART

Starts computation

MATHSTOP

Stops computation

MATHRESET

Resets computation

SAVEDISPLAY

Causes a timeout in
display data

SAVEEVENT

Causes a timeout in
event data

MESSAGE

Writes a message

SNAPSHOT

Takes a snapshot

MANUALSAMPLE

Performs manual
sampling

TIMERRESET

Resets the relative
timer

DISPLAYRATE1/2 Switches the trend

interval

DISPLAYGROUPCHANGE Switches the display group
FLAG

Raises a flag

TIMEADJUST

Adjusts the time

PANELLOAD

Loads settings

p5 Action details 1

p4 = TIMERRESET Timer number
p4 = DISPLAYGROUPCHANGE

Display group number

p4 = FLAG

Flag number

p4 = MESSAGE Message number (1 to

100)

p4 = PANELLOAD Setup file number (1 to

3)

p6 Action details 2

p4 = MESSAGE

Method of specifying
the destination to write
the message

ALL

All display groups

SELECT

A specific display group

p7 Action details 3

p4 = MESSAGE and p6 = SELECT

Display group number

Query

TU[p1]?

Example Use the remote control input (terminal 1) to execute

a memory start.
TUREMOTE,1,MEMORYSTART

Description • Set the numbers (such as the relay number

and internal switch number) by referring to the
table in section 3.3.

• Depending on the value of parameter p2 (event

type), there are some values that you cannot
select for parameter p4 (action type).

• Depending on other FX settings or the

installed options, there are some values that
you cannot select for parameter p4 (action
type).

• You can specify SNAPSHOT and

MANUALSAMPLE regardless of the FX
specifications. However, depending on
the FX specifications and the settings, the
corresponding functions may not operate.

• You cannot specify PANELLOAD on models

that do not have a CF card slot.

3.4 Setting Commands