App index, Tu sets an event action – Yokogawa Value Series FX1000 User Manual
Page 105
3-23
IM 04L21B01-17EN
Commands
1
2
3
4
5
6
App
Index
TU
Sets an event action
Syntax
TU p1,p2,p3,p4,p5,p6,p7
p1 Logic number (1 to 40)
p2 Event type
NONE
REMOTE
Remote control input
RELAY
Alarm output relay
SWITCH
Internal switch
ALARM
Alarm
TIMER
Timer
MATCHTIMETIMER Match time
USERKEY
USER key
p3 Event details
p2 = REMOTE
Remote number
p2 = RELAY
Relay number
p2 = SWITCH
Internal switch number
p2 = TIMER
Timer number
p2 = MATCHTIMETIMER
Match time timer
number
p2 = Any other value
Don’t care
p4 Action type
MEMORYSTART/STOP
Memory start or
memory stop
MEMORYSTART
Memory start
MEMORYSTOP
Memory stop
TRIGGER
Event trigger
ALARMACK
Alarm
acknowledgement
MATHSTART/STOP Starts or stops computation
MATHSTART
Starts computation
MATHSTOP
Stops computation
MATHRESET
Resets computation
SAVEDISPLAY
Causes a timeout in
display data
SAVEEVENT
Causes a timeout in
event data
MESSAGE
Writes a message
SNAPSHOT
Takes a snapshot
MANUALSAMPLE
Performs manual
sampling
TIMERRESET
Resets the relative
timer
DISPLAYRATE1/2 Switches the trend
interval
DISPLAYGROUPCHANGE Switches the display group
FLAG
Raises a flag
TIMEADJUST
Adjusts the time
PANELLOAD
Loads settings
p5 Action details 1
p4 = TIMERRESET Timer number
p4 = DISPLAYGROUPCHANGE
Display group number
p4 = FLAG
Flag number
p4 = MESSAGE Message number (1 to
100)
p4 = PANELLOAD Setup file number (1 to
3)
p6 Action details 2
p4 = MESSAGE
Method of specifying
the destination to write
the message
ALL
All display groups
SELECT
A specific display group
p7 Action details 3
p4 = MESSAGE and p6 = SELECT
Display group number
Query
TU[p1]?
Example Use the remote control input (terminal 1) to execute
a memory start.
TUREMOTE,1,MEMORYSTART
Description • Set the numbers (such as the relay number
and internal switch number) by referring to the
table in section 3.3.
• Depending on the value of parameter p2 (event
type), there are some values that you cannot
select for parameter p4 (action type).
• Depending on other FX settings or the
installed options, there are some values that
you cannot select for parameter p4 (action
type).
• You can specify SNAPSHOT and
MANUALSAMPLE regardless of the FX
specifications. However, depending on
the FX specifications and the settings, the
corresponding functions may not operate.
• You cannot specify PANELLOAD on models
that do not have a CF card slot.
3.4 Setting Commands