List of registers – Yokogawa Value Series FX1000 User Manual
Page 184
6-10
IM 04L21B01-17EN
List of Registers
Register
Description
Supplementary Information
Type
Access
Simultaneous
Access
Write
Read
406061
Internal switch 1
OFF: 0. ON: 1.
INT16
R
–
406062
Internal switch 2
OFF: 0. ON: 1.
INT16
R
–
406063
Internal switch 3
OFF: 0. ON: 1.
INT16
R
–
406064
Internal switch 4
OFF: 0. ON: 1.
INT16
R
–
406065
Internal switch 5
OFF: 0. ON: 1.
INT16
R
–
406066
Internal switch 6
OFF: 0. ON: 1.
INT16
R
–
406067
Internal switch 7
OFF: 0. ON: 1.
INT16
R
–
406068
Internal switch 8
OFF: 0. ON: 1.
INT16
R
–
406069
Internal switch 9
OFF: 0. ON: 1.
INT16
R
–
406070
Internal switch 10
OFF: 0. ON: 1.
INT16
R
–
406071
Internal switch 11
OFF: 0. ON: 1.
INT16
R
–
406072
Internal switch 12
OFF: 0. ON: 1.
INT16
R
–
406073
Internal switch 13
OFF: 0. ON: 1.
INT16
R
–
406074
Internal switch 14
OFF: 0. ON: 1.
INT16
R
–
406075
Internal switch 15
OFF: 0. ON: 1.
INT16
R
–
406076
Internal switch 16
OFF: 0. ON: 1.
INT16
R
–
406077
Internal switch 17
OFF: 0. ON: 1.
INT16
R
–
406078
Internal switch 18
OFF: 0. ON: 1.
INT16
R
–
406079
Internal switch 19
OFF: 0. ON: 1.
INT16
R
–
406080
Internal switch 20
OFF: 0. ON: 1.
INT16
R
–
406081
Internal switch 21
OFF: 0. ON: 1.
INT16
R
–
406082
Internal switch 22
OFF: 0. ON: 1.
INT16
R
–
406083
Internal switch 23
OFF: 0. ON: 1.
INT16
R
–
406084
Internal switch 24
OFF: 0. ON: 1.
INT16
R
–
406085
Internal switch 25
OFF: 0. ON: 1.
INT16
R
–
406086
Internal switch 26
OFF: 0. ON: 1.
INT16
R
–
406087
Internal switch 27
OFF: 0. ON: 1.
INT16
R
–
406088
Internal switch 28
OFF: 0. ON: 1.
INT16
R
–
406089
Internal switch 29
OFF: 0. ON: 1.
INT16
R
–
406090
Internal switch 30
OFF: 0. ON: 1.
INT16
R
–
407833 to
407834
Lot number
Valid range: 0 to 99999999
INT32_L
R/W
407835 to
407851
Batch number
Up to 17 registers (up to 33 characters with '¥0'
termination). The batch number must be 32
characters or less.
STR34
R/W
409503
Memory start or stop
Stop: 0. Start: 1.
INT16
R/W
409504
Alarm acknowledge
Applies to all alarms.
Execute alarm ACK: 1 (fixed)
Alarm off: 0. Alarm illuminated: 1. Alarm blinking
(occurring): 2. Alarm blinking (not occurring): 3
INT16
R/W
409506
Computation operation
Stop: 0. Start: 1. Reset: 2. Computation dropout
ACK: 4.
Stop: 0. Start: 1.
INT16
R/W
409512
Manual sampling start
or other action
Manual sampling: 0. Manual trigger: 1. Snapshot:
2.
INT16
W
410601
Preset message writing Message number (1 to 100)
INT16
W
410602
Message write destination
0: All groups. 1 to 10: Specified group number.
INT16
W
410603
Specified value.
INT16
W
410604 to
410610
(Reserved) Preset
message
-
-
-
6.3 Modbus Protocol Specifications