App index, Tg sets a color scale band, Tc sets the background color – Yokogawa Value Series FX1000 User Manual
Page 103: Tp sets automatic display group switching
3-21
IM 04L21B01-17EN
Commands
1
2
3
4
5
6
App
Index
TG
Sets a color scale band
Syntax
TG p1,p2,p3,p4,p5,p6,p7
p1 Measurement or computation channel
number
p2 Area (OFF, IN, OUT)
p3 Display color (24 colors; see the SL
command, which is used to set a trip line)
p4 Lower display position limit
p5 Upper display position limit
p6 Lower display position limit (exponent)
p7 Upper display position limit (exponent)
Query
TG[p1]?
Example Set the channel 005 color scale band to the
range from –1.0000 to 0.5000 V (2-V range), and
set the display color to green.
TG005,IN,GREEN,-10000,5000
Description • Parameters p6 and p7 are valid on models
with the Log scale (/LG1) option.
• Parameters p6 and p7 are valid when p1 is set
to a measurement channel.
• Configure the settings as shown below.
When using a channel that is not set to Log
scale (/LG1 option):
• Parameters p4 and p5 are the
corresponding channel’s span range (the
scaling range when scaling is enabled).
• Set the parameters so that p4 is less than
p5.
• Parameters p6 and p7 are Don’t care
values in setting commands. In queries,
these parameters will always be returned
as 0.
When using a channel that is set to Log scale
(/LG1 option):
• Parameters p4 and p5 are the mantissas of
the upper and lower limits, respectively, of
the color scale band.
• Parameters p6 and p7 are the exponents of
the upper and lower limits, respectively, of
the color scale band.
• The range defined by the display position
lower limit and the display position upper
limit is 1.00E–16 to 1.00E+16.
Mantissas p4 and p5
100 to 999: The corresponding values are
1.00 to 9.99.
Exponents p6 and p7
Parameter p6 must be between –16 and
16 when p4 is 100. Parameter p6 must be
between –16 and 15 when p4 is a value
other than 100. The same conditions hold
for the relationship between parameters p7
and p5.
• Set the parameters so that the lower
display position limits (p4 and p6) are less
than their upper display position limits (p5
and p7).
SQ
Sets the LCD brightness and the
screen backlight saver
Syntax
SQ p1,p2,p3,p4
p1 LCD brightness
1 to 8
p2 Screen backlight saver type
OFF
Disables the saver function
DIMMER Dims the backlight
TIMEOFF Turns off the backlight
p3 Amount of time until the FX switches to
saver mode
1MIN, 2MIN, 5MIN, 10MIN, 30MIN, 1H
p4 Event that causes the FX to return from
saver mode
KEY
Pressing of a key
KEY+ALM Pressing of a key or occurrence
of an alarm
Query
SQ?
Example Set the LCD brightness to 2 and the screen
backlight saver type to DIMMER. Set the amount
time of until the FX switches to saver mode to
5 minutes and the event that causes the FX to
return from saver mode to the pressing of a key.
SQ2,DIMMER,5MIN,KEY
Description If p2 is set to OFF, do not set p3 or p4.
TC
Sets the background color
Syntax
TC p1,p2
p1 Screen (WHITE, BLACK)
p2 Historical trend screen (WHITE, CREAM,
LIGHTGRAY, BLACK)
Query
TC?
Example Set the screen background color to black and
the historical trend screen background color to
cream.
TCBLACK,CREAM
TP
Sets automatic display group
switching
Syntax
TP p1
p1 Auto switching interval (5S, 10S, 20S, 30S,
1MIN)
Query
TP?
Example Switch between display groups at 5-second
intervals.
TP5S
3.4 Setting Commands