Tb sets the bar graph display, Sb sets the bar graph for a channel, Tn sets a scale – Yokogawa Value Series FX1000 User Manual
Page 102: Sv sets a measurement channel’s moving average, Sc sets a channel display color, Ta sets an alarm point mark
3-20
3.4 Setting Commands
IM 04L21B01-17EN
SE
Sets the line width and the
number of grid sections to use
on the trend graph
Syntax
SE p1,p2
p1 Trend line width (1 to 3) in dots
p2 Number of grid segments (4 to 12, AUTO)
Query
SE?
Example Set the trend waveform line width to 1 dot and
the number of grid segments to 10.
SE1,10
TB
Sets the bar graph display
Syntax
TB p1
p1 Bar graph display direction
HORIZONTAL
VERTICAL
Query
TB?
Example Display bar graphs horizontally.
TBHORIZONTAL
SB
Sets the bar graph for a channel
Syntax
SB p1,p2,p3
p1 Measurement or computation channel
number
p2 Bar graph base position
NORMAL Normal (lower limit)
CENTER
LOWER Lower limit
UPPER Upper limit
p3 Number of scale divisions (4 to 12)
Query
SB[p1]?
Example Set the number of scale divisions on the bar
graph for channel 002 to 5, and display the bar
graph from the span lower limit (the scaling lower
limit if scaling is enabled).
SB002,NORMAL,5
Description You can specify computation channels (including
in queries) on models with the /M1, /PM1, or
/PWR1 math option.
TN
Sets a scale
Syntax
TN p1,p2,p3
p1 Measurement or computation channel
number
p2 Display position (OFF, 1 to 6)
p3 Number of divisions (4 to 12, C10)
Query
TN[p1]?
Example Set the scale display position for channel 003 to
2, and set the number of divisions to 10.
TN003,2,10
Description You can specify computation channels (including
in queries) on models with the /M1, /PM1, or
/PWR1 math option.
SV
Sets a measurement channel’s
moving average
Syntax
SV p1,p2,p3
p1 Measurement channel number
p2 Moving average (OFF, ON)
p3 Number of moving average samples (2 to
400)
Query
SV[p1]?
Example Set the number of moving average samples for
channel 002 to 12.
SV002,ON,12
SC
Sets a channel display color
Syntax
SC p1,p2
p1 Measurement or computation channel
number
p2 Display color (see the SL command, which
is used to set a trip line)
Query
SC[p1]?
Example Set the channel 002 display color to blue.
SC002,BLUE
Description You can specify computation channels (including
in queries) on models with the /M1, /PM1, or
/PWR1 math option.
TA
Sets an alarm point mark
Syntax
TA p1,p2,p3,p4,p5,p6,p7
p1 Measurement or computation channel
number
p2 Mark kind
ALARM Alarm mark
FIXED Fixed mark
p3 Scale board display (ON, OFF)
p4 Alarm level 1 display color (24 colors; see
the SL command, which is used to set a trip
line)
p5 Alarm level 2 display color (24 colors; see
the SL command, which is used to set a trip
line)
p6 Alarm level 3 display color (24 colors; see
the SL command, which is used to set a trip
line)
p7 Alarm level 4 display color (24 colors; see
the SL command, which is used to set a trip
line)
Query
TA[p1]?
Example Display alarm marks on the channel 004 scale.
TA004,ALARM,ON
Description You can specify computation channels (including
in queries) on models with the /M1, /PM1, or
/PWR1 math option.