Using the Serial Communication Interface (/C2 and /C3 Options)

1

2

3

4

5

6

App

Index

RS-422A/485 Connection Procedure

Terminal arrangement and signal names

Connect a cable to the clamp terminal.

FG (Frame Ground)

本機器本体のケース接地です。

SG (Signal Ground)

信号用接地です。

SDB (Send Data B)

送信データB(+)です。

SDA (Send Data A)

送信データA(−)です。

RDB (Received Data B) 受信データB(+)です。
RDA (Received Data A) 受信データA(−)です。

2線式

FG SG SDB SDA RDB RDA

シールド電位

4線式

シールド

FG SG SDB SDA RDB RDA

(rear panel)

RS-422A/485 interface terminal

A serial communication terminal that

comes with the /C3 option

Each terminal corresponds to the signal indicated below.

Signal Name

Meaning

FG

Frame ground of the FX.

SG

Signal ground.

SDB

Send data B (+).

SDA

Send data A (–).

RDB

Receive data B (+).

RDA

Receive data A (–).

Connection

As shown in the figure below, remove approximately 5 mm of the covering from the end
of the cable to expose the conductor. Keep the exposed section from the end of the
shield within 5 cm.

Two-wire system

FG SG SDB SDA RDB RDA

Electric potential

of the shield

Four-wire system

Shield

FG SG SDB SDA RDB RDA

Connecting to the host device

The figure below illustrates the connection of the FX to a host device. If the port on the
host device is an RS-232 interface, connect a converter.

RS-422A/485

terminal on the FX

Host computer

or host device

Host device side

Converter

RS-422A/485

RS-422A/485

terminal on the FX

Host computer

RS-232

RS-422A/485

Host device side

2.3 Connecting the FX