Input Register (shared with the Modbus slave function)
• Common Items
• The client device can only read the input registers.
• Decimal position and unit are not included. Specify them on the client device.
• Details
Input Register Data
Data Type
300001
Measured data of measurement channel 001
16-bit signed integer
|
|
300012 Measured data of measurement channel 012
• There is no decimal position information.
301001
Alarm status of measurement channel 001
Bit string
|
|
301012 Alarm status of measurement channel 012
• Register structure and alarm status values
2
1
4
3
4 bits
4 bits
4 bits
4 bits
4-bits
value Meaning
0
No alarm
1
High limit alarm
2
Low limit alarm
3
Difference high limit alarm
4
Difference low limit alarm
5
High limit on rate-of-change alarm
6
Low limit on rate-of-change alarm
7
Delay high limit alarm
8
Delay low limit alarm
Alarm level
Alarm status
302001
Lower bytes of the computed data of computation channel 101
32-bit signed integer
302002
Higher bytes of the computed data of computation channel 101
|
|
302047
Lower bytes of the computed data of computation channel 124
302048
Higher bytes of the computed data of computation channel 124
• Register structure
Example: Channel 101
Higher bytes
Lower bytes
Register 302002
Computed data
Register 302001
• There is no decimal position information.
303001
Alarm status of computation channel 101
Bit string
|
303024
Alarm status of computation channel 124
• The register structure and alarm status values are the same as the alarm status of
measurement channels.
6.3 Modbus Protocol Specifications