Running a series 982 profile, Resume a profile, Run menu – Watlow Series 982 User Manual
Page 99
WATLOW Series 982 User’s Manual
7.5
Programming, Chapter 7
Run Menu
Running a Series 982 Profile
You can run your Series 981/982 profile from anywhere except the Setup
menus or Factory menus or when the control is auto-tuning. Press the
Hold/Run key once. The RUN LED begins flashing, and the lower display
flashes FiLE and asks what FiLE is to be run. Use the Up or Down keys
to select the file number in the upper display, choices are 1, 2, 3, or 4.
Press the Mode key and the lower display flashes StEP and asks what
StEP is to be run. Use the Up or Down keys to select the StEP number in
the upper display, choices are 1 through 6. Press the Hold/Run key once
again, your profile begins, and the RUN LED is lit. If you decide not to
run a profile, press the Display key to exit the Pre-Run menu.
If the none of the keys are pressed within 1 minute, the RUN function will
abort. While the profile is Running, you can only view the RUN menu.
Press the Mode key to advance you through the RUN menu. For more
information on the RUN menu see Chapter 7.
Resume a Profile
To resume a halted profile, press the Hold/Run key once. Press the Mode
key to advance to the rESU parameter. The lower display will show rESU
and the upper display will show the file and step number that will be
resumed (file-step). Press the Hold/Run key again, the profile resumes,
and the RUN LED is lit. You can only resume at the exact step you left
off on. If you halt a running profile and make changes, you cannot
resume the profile. The rESU parameter only appears when a running
profile is halted.
To Run your profile...
Press the Hold/Run key twice.
To Stop a running profile...
Press the Hold/Run key once.
To Resume a halted profile...
Press the Hold/Run key, press the Mode