Event input 1, Setup-global – Watlow Series 982 User Manual
Page 56
4.30
WATLOW Series 982 User’s Manual
Setup Menus, Chapter 4
Setup-Global
Event Input 1
Select the effect of closing the event input 1 switch.
• [``no] disables event input 1.
• [`LOC] locks out the front panel keys.
• [`ALr] resets an alarm.
• [`OFF] turns all control outputs off (de-energize relays, but does not hold
program).
• [hold] puts the controller into hold mode (ends the program and holds the
last set point).
• [FiL1] [FiL2] [FiL3] or [FiL4] starts file 1, 2, 3 or 4.
• [AbSP] controls to the abort set point.
• [PAuS] pauses a running profile.
• [`WE] can be configured as a waitfor event input.
[`Ei1] This prompt always appears.
Default
↓
[``no] [`LOC] [`ALr] [`OFF] [Hold] [FIL1] … [FIL4] [AbSP] [PAuS] [`WE]