Input 1 wiring, 8 input 1 wiring, Thermocouple – Watlow Series 982 User Manual
Page 18: Rtd (2- or 3-wire), Figure 2.8c, 98 _ c - 1 _ _ _ - _ _ _ _ (no dip switches), 98 _ c - 2, Figure 2.8d, 98 _ c - 2 _ _ _ - _ _ _ _ input impedance: 7 ω
2 . 8
WATLOW Series 982 User’s Manual
Installation and Wiring, Chapter 2
Input 1 Wiring
Figure 2.8c —
0-5VО
О, 1-5VО
О or 0-10VО
О (dc) Process
Universal signal conditioner
98 _ C - 2 _ _ _ - _ _ _ _
Input impedance: 10K
Ω
Figure 2.8a —
Thermocouple
Thermocouple only
98 _ C - 1 _ _ _ - _ _ _ _ (no DIP switches)
Universal signal conditioner
98 _ C - 2 _ _ _ - _ _ _ _
Input impedance: 20M
Ω
Figure 2.8b —
RTD (2- or 3-wire)
Universal signal conditioner
98 _ C - 2 _ _ _ - _ _ _ _
9
10
8
S2
S1
S3
10
9
-
+
Figure 2.8d —
0-20mA or 4-20mA Process
Universal signal conditioner
98 _ C - 2 _ _ _ - _ _ _ _
Input impedance: 7
Ω
10
8
-
+
9
10
8
S2
S1
DIP Switch
Setting
R, S, B
DIP Settings
J, K, T, N, C, E, D, Pt2,
DIP Settings
DIP Switch
Setting
DIP Switch
Setting
˜
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
O
N
↑
1
2
3
O
N
↑
1
2
3
O
N
↑
1
2
3
O
N
↑
1
2
3
O
N
↑
1
2
3
9
10
+
-
Jumper
9 to 10
for 2-wire
RTD
ç
CAUTION:
An external resistor
is required for
0-20mA and 4-20mA
process wiring to
prevent a high in-
rush current which
could burn out the
controller’s 7-ohm
resistor. See page 2.5
for recommenda-
tions.