4.8
WATLOW Series 982 User’s Manual
Setup Menus, Chapter 4
Setup-Input
NOTE:
If [``no] is selected
for [`In2] none of
the other input 2
prompts will
appear.
Input 2
Select sensor type for input 2. This selection must match the sensor
type connected to terminals 18, 19 and 20. See Appendix for more infor-
mation about sensors.
• Changing the value of [`In2] changes all other prompts to the facto-
ry default values, except the Communications and Lockout menus,
the [`C_F] prompt in the Global Menu and the [`dFL] prompt in the
Calibration Menu. If you change the value, the default warning
[dFLt] will flash in the upper display.
• Changes do not take effect automatically after five seconds; you must
press the Mode key µ to enter the sensor type change and advance to
the next prompt.
[`In2] This prompt and other Input 2 prompts appear only on controllers
equipped with input 2 hardware (not 98__-_0__-____).
If
Default
↓
↓
98__-3___-____
no DIP
slidewire
[``no]
[SLid]
resistance
[`In2]
[`In2]
only
98__-5___-____
no DIP
event 2
[``no]
[`Ei2]
digital event
[``In2]
[`In2]
only
Range Low 2
Select the low resistance of the slidewire potentiometer.
[`rL2] This prompt appears only on controllers with [`In2] (Input Menu)
set to [SLiD].
Default
↓
[```0] … [`rH2]
[`rL2]
[`rL2]
[`In2]
ç
CAUTION:
Changing the value
of [`In2] changes
most other prompts
to the factory
default values and
clears all program
steps. Verify the
correct sensor type
before making a
change. Document
all settings before
changing input
type. Failure to fol-
low this guideline
could result in dam-
age to equipment or
property.
NOTE:
See Chapter 9 for
more information
on slidewire feed-
back.
[`rL2]
NOTE:
These values do not
affect the low or the
high set point limit
for process alarms.
NOTE:
If [SLid] is selected
for [`In2], [`Ot2]
prompt will not
appear.