Operation Menus, Chapter 5
Operation-PID
Output 1 Rate
Tune the rate to eliminate overshoot on startup or after the set
point changes.
The rate setting will not influence the percent power if the
process value is more than twice the proportional band from the set point.
When set to [`)00], rate is disabled.
[`rA1] This prompt appears only if [`dfL] (Calibration Menu) is set to
[``US] and [`Pb1] is set higher than [```0].
Default
↓
[`)00] … [`(99]
min
.
[`rA1]
[`rA1]
Output 1 Derivative
Tune the derivative to eliminate overshoot on startup or after the set
point changes.
The derivative setting will not influence the percent power
if the process value is more than twice the proportional band from the set
point. When set to [`)00], derivative is disabled.
[`dE1] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``SI] and [`Pb1] is set higher than [```0].
Default
↓
[`)00] … [`(99]
min.
[`dE1]
[`dE1]
[`rA1]
[`dE1]