Latching 4, Silencing 4, Sil4] [lat4 – Watlow Series 982 User Manual
Page 50: Setup-output

4.24
WATLOW Series 982 User’s Manual
Setup Menus, Chapter 4
Setup-Output
Latching 4
Select whether alarm 4 will be latching or non-latching. A latching
alarm [`LAT] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.
[LAt4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98__-____-_B__, 98__-____-_J__ or 98__-____-_K__) or
switched dc (98__-____-_C__) and with [`Ot4] set to [`AL4] or [AL4n].
Default
↓
[`nLA]
[`LAt]
[LAt4]
[LAt4]
Silencing 4
Select silencing to inhibit alarm 4 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.
• Silencing disables the alarm until the signal is between [A4LO] and
[A4HI].
[SIL4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98__-____-_B__, 98__-____-_D__ , 98__-____-_E__ or
98__-____-_K__) or switched DC (98__-____-_C__) and with [`Ot4] set to
[`AL4] or [AL4n].
Default
↓
[`OFF]
[``On]
[SIL4]
[SIL4]
˜
NOTE:
See Chapter 8 for
more information
on alarms.
[SIL4]
[LAt4]