Page 50: Setup-output

background image

4.24

WATLOW Series 982 User’s Manual

Setup Menus, Chapter 4

Setup-Output

Latching 4

Select whether alarm 4 will be latching or non-latching. A latching
alarm [`LAT] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.

[LAt4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98__-____-_B__, 98__-____-_J__ or 98__-____-_K__) or
switched dc (98__-____-_C__) and with [`Ot4] set to [`AL4] or [AL4n].

Default

[`nLA]

[`LAt]

[LAt4]

[LAt4]

Silencing 4

Select silencing to inhibit alarm 4 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.

• Silencing disables the alarm until the signal is between [A4LO] and

[A4HI].

[SIL4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98__-____-_B__, 98__-____-_D__ , 98__-____-_E__ or
98__-____-_K__) or switched DC (98__-____-_C__) and with [`Ot4] set to
[`AL4] or [AL4n].

Default

[`OFF]

[``On]

[SIL4]

[SIL4]

˜

NOTE:
See Chapter 8 for
more information
on alarms.

[SIL4]

[LAt4]