Analog output, Process 3, Aout] [prc3 – Watlow Series 982 User Manual
Page 51: Setup-output
WATLOW Series 982 User’s Manual
4.25
Setup Menus, Chapter 4
Setup-Output
Analog Output
Select which value to retransmit as the output 3 signal.
• [Prc1] retransmits the process 1 value.
• [StPt] retransmits the set point.
• [Prc2] retransmits the process 2 value. This prompt appears only if the
controller is equipped with input 2 hardware and if [`In2] is not set to
[``no] or [`Ei2].
• [``no] turns off retransmit function.
[Aout] This prompt appears only on controllers equipped with retransmit
hardware (98__-____-M___ or 98__-____-N___).
Default
↓
[Prc1]
[StPt]
[Prc2]
[``no]
[Aout]
[Aout]
[Aout]
[Aout]
Process 3
Select the range for the retransmit signal at output 3.
[Prc3] This prompt appears only on controllers equipped with retransmit
hardware (98__-____-M___ or 98__-____-N___) and with [Aout] not set to
[``no].
Default
↓
4-20mA
0-20mA
0-5VÎ
1-5VÎ
0-10VÎ (dc)
[4-20]
[0-20]
[`0-5]
[`1-5]
[0-10]
[Prc3]
[Prc3]
[Prc3]
[Prc3]
[Prc3]
˜
NOTE:
See Chapter 9 for
more information
on retransmit.
[Aout]