External power supply, 5 external power supply dip switches, Dip switches – Watlow Series 982 User Manual
Page 9: External power supply dip switches (option “t”)
WATLOW Series 982 User’s Manual
1.5
DIP Switches
Starting Out with the Watlow Series 982, Chapter 1
External Power Supply DIP Switches (Option “T”)
Models equipped with an external signal conditioner power supply (Option
“T”), have a DIP switch for selecting the power supply voltage. Output 2, 3
or 4 can be ordered with the external power supply. The location of each
board and DIP switch appear below. When the control leaves the factory,
both switches are off. The figures below show a PC board cutaway for each
DIP switch. See the table to the left
for the power supply switch set-
tings. The settings can be used for
all three output DIP switches. For
other voltage or current ratings con-
tact the factory.
Figure 1.5a -
Output 2
External Signal
Conditioner
Power Supply.
Figure 1.5b -
Output 3
External Signal
Conditioner
Power Supply.
Figure 1.5c -
Output 4
External Signal
Conditioner
Power Supply.
98
_ C - _ _ _ T - _ _ _ _
98
_ C - _ _ _ _ - T _ _ _
98
_ C - _ _ _ _ - _ T _ _
Voltage/Load Current
S1
S2
5V ±5% @ 30mA
On
On
12V ±5% @ 30mA
On
Off
20V ±5% @ 30mA
Off
Off
Table 1.5 -
Power Supply DIP