Output 4, Alarm 4, Setup-output – Watlow Series 982 User Manual
Page 48
4.22
WATLOW Series 982 User’s Manual
Setup Menus, Chapter 4
Setup-Output
Output 4
Set the way that output 4 will respond to a difference between the set
point and an input variable.
• [`AL4] de-energizes output 4 in an alarm condition.
• [AL4n] energizes output 4 in an alarm condition.
• [Ent4] sets output 4 to an event output.
[`Ot4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98__-____-_B__, 98__-____-_D__ , 98__-____-_E__ or
98__-____-_K__) or switched dc (98__-____-_C__).
Default
↓
[`AL4]
[AL4n]
[Ent4] [``no]
[`Ot4]
[`Ot4]
[`Ot4]
[`Ot4]
Alarm 4
Select the alarm type for alarm 4.
• [`Pr1] uses a process signal from input 1.
• [`dE1] uses a deviation from the input 1 signal.
• [rAtE] uses the rate of change at input 1 in degrees per minute.
[`AL4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98__-____-_B__, 98__-____-_D__ , 98__-____-_E__ or
98__-____-_K__) or switched DC (98__-____-_C__) and [`Ot4] is set to
[`AL4] or [AL4n].
Default
↓
[`Pr1]
[`dE1]
[rAtE]
[`AL4]
[`AL4]
[`AL4]
[`AL4]
˜
NOTE:
See Chapter 8 for
more information
on alarms.
[`Ot4]