beautypg.com

Output 2 wiring, 12 output 2 wiring, Switched dc, open collector – Watlow Series 982 User Manual

Page 22: External signal conditioner power supply, Ac outputs

background image

2 . 1 2

WATLOW Series 982 User’s Manual

Installation and Wiring, Chapter 2

Output 2 Wiring

Figure 2.12b —

Switched DC, Open Collector

98 _ C - _ _ _ C - _ _ _ _

Minimum load resistance: 500

15

External

Load

+

16

17

-

COM

Figure 2.12d —

0-5VО

О, 1-5VО

О and 0-10VО

О (DC) Process

98 _ C - _ _ _ F - _ _ _ _

Minimum load impedance: 1K

Figure 2.12c —

0-20mA and 4-20mA Process

98 _ C - _ _ _ F - _ _ _ _

Maximum load impedance: 800

15

+

-

17

16

+

-

17

Figure 2.12e —

External Signal Conditioner Power Supply

98 _ C - _ _ _ T - _ _ _ _

15

16

1

2

+

-

+V

-V

Transmitter

4-20mA out

Input
1 or 2

+

-

Figure 2.12a —

AC Outputs

Solid-state Relay with Contact Suppression

98 _ C - _ _ _ B - _ _ _ _

0.5 amps, minimum off-state impedance: 20K

Electromechanical Relay with Contact Suppression
(NO and COM contacts only)

98 _ C - _ _ _ D - _ _ _ _

Form C, 5 amps, minimum off-state impedance: 20K

Electromechanical Relay without Contact Suppression

98 _ C - _ _ _ E - _ _ _ _

Form C, 5 amps off-state impedance: 31M

Solid-state Relay without Contact Suppression

98 _ C - _ _ _ K - _ _ _ _

0.5 amps, off-state impedance: 31M

External

Load

COM

L1

L2

Fuse

NO

15

16

NC

17

(#17 for D & E outputs only)

+ Vdc

Internal Circuitry

15

16

17

790

19 to 32VÎ (dc)

˜

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

˜

NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter connect-
ed to input 1.

˜

NOTE:
See Chapter 1 for
DIP switch location
and settings.

NOTE:
This output cannot
be configured as an
event ouput.

NOTE:
If
[SLid] is selected
for
[`In2], [`Ot2]
prompt will not
appear.

This manual is related to the following products: