Styp, Stpt, Hour – Watlow Series 982 User Manual

Page 96: Rate, Ent3, Program menu

background image

7.2

WATLOW Series 982 User’s Manual

Programming, Chapter 7

Program Menu

[StYP]

Step Type:

Choose from five different step types. When selecting Step

1, you will not see the jump-loop (JL) or link file (LFiL) step type.
Range:

StPt, SoAh, JL, LFiL or End

Default:

End

[StPt]

Set Point Step (StPt) : The following parameters are associated
with the set point step.

[``SP]

Set Point

: The temperature the system tries to achieve for this step. This

is done linearly, producing a ramp from a beginning set point to this end
set point.
Range:

rL1 to rH1

Default:

75°F/24°C or rL value if rL

≥75°F/24°C or if rH≤75°F/24°C

[Hour]

Hour:

The number of hours, plus the Min and SEC parameters equal the

total step time to achieve the temperature under the StPt step type.
Range:

0 to 99

Default:

0

Hidden if: PtYP = rAtE

[Min]

Minutes:

The number of minutes plus the Hour and SEC parameters

equal the total step time to achieve the temperature under the StPt step
type.
Range:

0 to 59

Default:

0

Hidden if: PtYP = rAtE

[`SEC]

Seconds:

The number of seconds plus the Hour and Min parameters

equal the total step time to achieve the temperature under the StPt step
type.
Range:

0 to 59

Default:

0

Hidden if: PtYP = rAtE

[rAte]

Rate:

Represents the rate at which the set point changes in degrees per

minute. Decimal point location dependent on dEC1 (decimal 1) prompt.
Range:

0.0 to 360.0°F/0.0 to 200.0°C or 0.0 to 360.0 units

Default:

0.0

Hidden if: PtYP = ti

[Ent3]

Event 3:

Selects whether Event 3 is on or off.

Range:

On or OFF

Default:

OFF

Hidden if: Hardware not present or Ot3 = AL3, AL3n or no

NOTE:
Decimal points may
not always be in the
position specified
depending on the
value of Decimal 1
in the Input Menu.