Input prompts, 3 input prompts, Setup-input – Watlow Series 982 User Manual
Page 29: Input 1
Input Prompts
When you are in the Setup menus, the Series 982 displays the menu selec-
tion ( [InPt], [OtPt], [GLbL] or [COM] ) in the upper display, and [`SEt] in
the lower display.
The Up-arrow > or Down-arrow key < selects another menu. Press the
Mode key µ to display the prompt in the lower display and its value in the
upper display. Use the Up-arrow > or Down-arrow < key to change the
value in the upper display. The new value will not take effect until after a
five-second delay or until you press the Mode key µ.
Input 1
Select sensor type for input 1. This selection must match the sensor type
connected to terminals 8, 9 and 10. See Appendix for more information
about sensors.
• Changing the value of [`In1] changes all other prompts to the factory
default values, except the Communications and Lockout menus, the
[`C_F] prompt in the Global Menu and the [`dFL] prompt in the
Calibration Menu. If you change the value, the default warning [dFLt]
will flash in the upper display.
• Changes do not take effect automatically after five seconds; you must
press the Mode key µ to enter the sensor type change and advance to
the next prompt.
[`In1] This prompt always appears.
If
Default
↓
↓
98__-1___-____
no DIP
J
K
T
N
E
W5
W3
Pt2
[```J] [```H] [```t] [```n] [```E] [```C] [```d] [`Pt2]
thermocouple
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
only
98__-2___-____
Input 1 DIP
J
K
T
N
E
W5
W3
Pt2
[```J] [```H] [```t] [```n] [```E] [```C] [```d] [`Pt2]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
[`In1]
thermocouple
Input 1 DIP
R
S
B
[```r] [```S] [```b]
[`In1]
[`In1]
[`In1]
thermocouple
O
N
↑
1
2
3
O
N
↑
1
2
3
WATLOW Series 982 User’s Manual
4.3
Setup Menus, Chapter 4
Setup-Input
˜
NOTE:
Decimal points may
not always be in the
position specified
below depending on
the the settings in
the Decimal 1
[dEC1] parameter in
the Input Menu.
ç
CAUTION:
Changing the value
of [`In1] changes
most other prompts
to the factory
default values and
clears all program
steps. Verify the
correct sensor type
before making a
change. Document
all settings before
changing sensor
type. Failure to fol-
low this guideline
could result in dam-
age to equipment or
property.
[`In1]
Input 1 continued
on next page.
[`In1]