Output 1 wiring, 11 output 1 wiring, Ac outputs – Watlow Series 982 User Manual
Page 21: Switched dc, open collector
WATLOW Series 982 User’s Manual
2 . 1 1
Installation and Wiring, Chapter 2
˜
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Figure 2.11a —
AC Outputs
Solid-state Relay with Contact Suppression
98 _ C - _ _ B _ - _ _ _ _
0.5 amps, minimum off-state impedance: 20K
Ω
Electromechanical Relay with Contact Suppression
(NO and COM contacts only)
98 _ C - _ _ D _ - _ _ _ _
Form C, 5 amps, minimum off-state impedance: 20K
Ω
Electromechanical Relay without Contact Suppression
98 _ C - _ _ E _ - _ _ _ _
Form C, 5 amps off-state impedance: 31M
Ω
Solid-state Relay without Contact Suppression
98 _ C - _ _ K _ - _ _ _ _
0.5 amps, off-state impedance: 31M
Ω
Output 1 Wiring
Figure 2.11b —
Switched DC, Open Collector
98 _ C - _ _ C _ - _ _ _ _
Minimum load resistance: 500
Ω
External
Load
COM
L1
L2
Fuse
NO
12
13
NC
14
(#14 for D & E outputs only)
12
External
Load
+
13
14
-
COM
Figure 2.11d —
0-5VО
О, 1-5VО
О and 0-10VО
О (DC) Process
98 _ C - _ _ F _ - _ _ _ _
Minimum load impedance: 1K
Ω
Figure 2.11c —
0-20mA and 4-20mA Process
98 _ C - _ _ F _ - _ _ _ _
Maximum load impedance: 800
Ω
14
-
+
12
14
-
+
13
+ Vdc
Internal Circuitry
12
13
14
790
Ω
19 to 32VÎ (dc)