beautypg.com

Output 1 wiring, 11 output 1 wiring, Ac outputs – Watlow Series 982 User Manual

Page 21: Switched dc, open collector

background image

WATLOW Series 982 User’s Manual

2 . 1 1

Installation and Wiring, Chapter 2

˜

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

Figure 2.11a —

AC Outputs

Solid-state Relay with Contact Suppression

98 _ C - _ _ B _ - _ _ _ _

0.5 amps, minimum off-state impedance: 20K

Electromechanical Relay with Contact Suppression
(NO and COM contacts only)

98 _ C - _ _ D _ - _ _ _ _

Form C, 5 amps, minimum off-state impedance: 20K

Electromechanical Relay without Contact Suppression

98 _ C - _ _ E _ - _ _ _ _

Form C, 5 amps off-state impedance: 31M

Solid-state Relay without Contact Suppression

98 _ C - _ _ K _ - _ _ _ _

0.5 amps, off-state impedance: 31M

Output 1 Wiring

Figure 2.11b —

Switched DC, Open Collector

98 _ C - _ _ C _ - _ _ _ _

Minimum load resistance: 500

External

Load

COM

L1

L2

Fuse

NO

12

13

NC

14

(#14 for D & E outputs only)

12

External

Load

+

13

14

-

COM

Figure 2.11d —

0-5VО

О, 1-5VО

О and 0-10VО

О (DC) Process

98 _ C - _ _ F _ - _ _ _ _

Minimum load impedance: 1K

Figure 2.11c —

0-20mA and 4-20mA Process

98 _ C - _ _ F _ - _ _ _ _

Maximum load impedance: 800

14

-

+

12

14

-

+

13

+ Vdc

Internal Circuitry

12

13

14

790

19 to 32VÎ (dc)

This manual is related to the following products: