Latching 3, Silencing 3, Lat3] [sil3 – Watlow Series 982 User Manual
Page 47: Setup-output
WATLOW Series 982 User’s Manual
4.21
Setup Menus, Chapter 4
Setup-Output
Latching 3
Select whether alarm 3 will be latching or non-latching. A latching
alarm [`LAt] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.
[LAt3] This prompt appears only on controllers equipped with output 3
hardware for a relay (98__-____-B___, 98__-____-J___ or 98__-____-K___) or
switched dc (98__-____-C___) and with [`Ot3] set to [`AL3] or [AL3n].
Default
↓
[`nLA]
[`LAt]
[LAt3]
[LAt3]
Silencing 3
Select silencing to inhibit alarm 3 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.
• Silencing disables the alarm until the signal is between [A3LO] and
[A3HI].
[SIL3] This prompt appears only on controllers equipped with output 3
hardware for a relay (98__-____-B___, 98__-____-J___ or 98__-____-K___) or
switched dc (98__-____-C___) and with [`Ot3] set to [`AL3] or [AL3n].
Default
↓
[`OFF]
[``On]
[SIL3]
[SIL3]
˜
NOTE:
See Chapter 8 for
more information
on alarms.
[LAt3]
[SIL3]