beautypg.com

Output 4 wiring, 14 output 4 wiring, Switched dc, open collector – Watlow Series 982 User Manual

Page 24: Ac outputs, External signal conditioner power supply

background image

Figure 2.14b —

Switched DC, Open Collector

98 _ C - _ _ _ _ - _ C _ _

Minimum load resistance: 500

Figure 2.14a —

AC Outputs

Solid-state Relay with Contact Suppression

98 _ C - _ _ _ _ - _ B _ _

0.5 amps, minimum off-state impedance: 20K

Electromechanical Relay with Contact Suppression
(NO and COM contacts only)

98 _ C - _ _ _ _ - _ D _ _ _

Form C, 5 amps, minimum off-state impedance: 20K

Electromechanical Relay without Contact Suppression

98 _ C - _ _ _ _ - _ E _ _ _

Form C, 5 amps, off-state impedance: 31M

Solid-state Relay without Contact Suppression

98 _ C - _ _ _ _ - _ K _ _ _

0.5 amps, off-state impedance: 31M

2 . 1 4

WATLOW Series 982 User’s Manual

Installation and Wiring, Chapter 2

Output 4 Wiring

External

Load

COM

L1

L2

Fuse

NO

5

6

NC

(#7 for D & E outputs only)

7

5

External

Load

6

+

7

-

COM

Figure 2.14c —

External Signal Conditioner Power Supply

98 _ C - _ _ _ _ - _ T _ _

5

6

+

-

+V

-V

Transmitter

4-20mA out

Input
1 or 2

+

-

For data communications wiring refer to Data Communications
with the Watlow Series 988 Family of Controllers.

˜

NOTE:
Input-to-output iso-
lation is defeated
when the external
transmitter power
supply is used to
power a signal con-
ditioner connected
to input 1.

˜

NOTE:
See Chapter 1 for
power supply DIP
switch information.

˜

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

+ Vdc

Internal Circuitry

5

6

7

790

19 to 32VÎ (dc)

This manual is related to the following products: