WATLOW Series 982 User’s Manual
2 . 1 3
Installation and Wiring, Chapter 2
Figure 2.13c —
Process Retransmit
0-20mA, 4-20mA, Load impedance: 600
Ω max.
98 _ C - _ _ _ _ - M _ _ _
0 - 5 VО
О, 1-5VО
О, 0-10VО
О (dc), Load impedance: 500
Ω min.
98 _ C - _ _ _ _ - N _ _ _
˜
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter con-
nected to input 1.
˜
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Figure 2.13d —
External Signal Conditioner Power Supply
98 _ C - _ _ _ _ - T _ _ _
Figure 2.13a —
AC Outputs
Solid-state Relay with Contact Suppression
98 _ C - _ _ _ _ - B _ _ _
0.5 amps, minimum off-state impedance: 20K
Ω
Electromechanical Relay without Contact
Suppression
98 _ C - _ _ _ _ - J _ _ _ _
Form A or B, 5 amps, off-state impedance: 31M
Ω
Solid-state Relay without Contact Suppression
98 _ C - _ _ _ _ - K _ _ _ _
0.5 amps, off-state impedance: 31M
Ω
External
Load
COM
L1
L2
Fuse
NO Form A
1
2
NC Form B
or
Figure 2.13b —
Switched DC
98 _ C - _ _ _ _ - C _ _ _
Minimum load resistance: 500
Ω
1
2
External
Load
-
+
1
2
+
-
+V
-V
Transmitter
4-20mA out
Input
1 or 2
+
-
Form B
Form A
Form A or B
alarm jumper
settings (98_C-
____-J___ only)
+ Vdc
Internal Circuitry
1
2
790
Ω
19 to 32VÎ (dc)
1
2
+
-
Output 3 Wiring
˜
NOTE:
See Chapter 1 for
DIP switch location
and settings.