Operation-PID
Output 1 Reset
Tune the control action to eliminate the offset or droop between the
set point and the actual process value for PID output 1.
When set to
[`)00], reset is disabled.
[`rE1] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``US] and [`Pb1] is not set to [```0].
Default
↓
[`)00 … [`(99]
repeats/min.
[`rE1]
[`rE1]
Output 1 Integral
Tune the control action to eliminate the offset or droop between the
set point and the actual process value for PID output 1.
When set to
[`)00], integral is disabled.
[`It1] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``S1] and [`Pb1] is not set to [```0].
Default
↓
[`)00] … [9(99]
min. / repeat
[`It1]
[`It1]
[`rE1]
[`It1]