5.12

WATLOW Series 982 User’s Manual

Operation Menus, Chapter 5

Operation-PID

Output 1 Reset

Tune the control action to eliminate the offset or droop between the
set point and the actual process value for PID output 1.

When set to

[`)00], reset is disabled.

[`rE1] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``US] and [`Pb1] is not set to [```0].

Default

[`)00 … [`(99]

repeats/min.

[`rE1]

[`rE1]

Output 1 Integral

Tune the control action to eliminate the offset or droop between the
set point and the actual process value for PID output 1.

When set to

[`)00], integral is disabled.

[`It1] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``S1] and [`Pb1] is not set to [```0].

Default

[`)00] … [9(99]

min. / repeat

[`It1]

[`It1]

[`rE1]

[`It1]