Output 1 cycle time, Output 2 proportional band, Pb2] [`ct1 – Watlow Series 982 User Manual
Page 82: Operation-pid
5.14
WATLOW Series 982 User’s Manual
Operation Menus, Chapter 5
Operation-PID
Output 1 Cycle Time
Select the time, in seconds, of a complete on/off cycle.
[`Ct1] This prompt appears only if [`In1] (Input Menu) is not set to a
process and [`Pb1] is set higher than [```0].
If
Default
↓
↓
mechanical
[``%0] … [`1)0] … [99(9]
sec.
relay
[`Ct1]
[`Ct1]
[`Ct1]
outputs
open collector
[brSt]
[``)1] … [``!0] … [99(9]
sec.
or solid-state
[`Ct1]
[`Ct1]
[`Ct1]
[`Ct1]
relay outputs
Output 2 Proportional Band
Select the proportional band for PID output 2.
If set to [```0] it func-
tions as an on/off control and the switching differential is determined by
the [HYS2] value (Output Menu).
[`Pb2] This prompt appears only if [`Ot2] (Output Menu) is set to [``Ht]
or [``CL] .
If
Default
↓
↓
[``US]
& [``°F]
[```0] … [[``25] … [`999]
[`dFL]
[`C_F]
[`Pb1]
[`Pb1]
[`Pb1]
(Calibration Menu)
(Global Menu)
& [`r†d]
[``)0] … [[``25] … [99(9]
[`In1]
[`Pb1]
[`Pb1]
[`Pb1]
(Input Menu)
[``US]
& [``°C]
[```0] … [[``14] … [`555]
[`dFL]
[`C_F]
[`Pb1]
[`Pb1]
[`Pb1]
(Calibration Menu)
(Global Menu)
& [`r†d]
[``)0] … [[``14] … [99(9]
[`In1]
[`Pb1]
[`Pb1]
[`Pb1]
(Input Menu)
[``SI]
[``)0] … [``#0] … [`9(9]
% of span
[`dFL]
[`Pb1]
[`Pb1]
[`Pb1]
(Calibration Menu)
[`Pb2]
[`Ct1]
NOTE:
For more informa-
tion on burst fire,
[brSt], see
Chapter 9.