Output 2, Process 2, Ot2] [prc2 – Watlow Series 982 User Manual
Page 41: Setup-output
WATLOW Series 982 User’s Manual
4.15
Setup Menus, Chapter 4
Setup-Output
Output 2
Set the way that output 2 will respond to a difference between the set
point and an input variable.
• [`AL2] de-energizes output 2 in an alarm condition.
• [AL2n] energizes output 2 in an alarm condition.
• [``Ht] select reverse action, so that output 2 responds when the input
signal is less than the set point. This prompt only appears if [`Ot1] is set
to [``CL].
• [``CL] select direct action, so that output 2 responds when the input
signal is more than the set point. This prompt only appears if [`Ot1] is
set to [``Ht].
[`Ot2] This prompt appears only on controllers equipped with output 2
hardware (not 98__-___A-____). [`AL2] and [AL2n] do not appear if output 2
is a process output (98__-___F-____). [``Ht] and [``CL] do not appear if
[AL90] (in the Global Menu) is set to [dUPL].
Default
↓
[``no]
[`AL2]
[Al2n]
[``Ht] or [``CL]
[`Ot2]
[`Ot2]
[`Ot2]
[`Ot2]
[`Ot2]
Process 2
Select the process range for output 2.
[Prc2] This prompt appears only on controllers equipped with output 2
process hardware (98__-___F-____) and with [`Ot2] not set to [``no].
Default
↓
4-20mA
0-20mA
0-5VÎ
1-5VÎ
0-10VÎ (dc)
[4-20]
[0-20]
[`0-5]
[`1-5]
[0-10]
[Prc2]
[Prc2]
[Prc2]
[Prc2]
[Prc2]
[`Ot2]
[Prc2]
NOTE:
[`Ot2] prompt will
not appear if
[SLid] is selected
for [`In2].