6. Parameter Settings

80

z

Default standstill mode (No.53 CTLF)

This parameter defines the power-saving mode to be applied when the actuator stands by for a long time while

the machine is operating; the actuator stands by for a long time after completing home return operation; or the

actuator stands by for a long time after completing positioning operation in the numerical specification mode.

Define whether to enable or disable power-saving in parameter No. 53.

Setting

All power-saving modes are disabled.

0

Full servo control mode

4

The factory setting is “0 [Disable].”

Full servo control mode

The pulse motor is servo-controlled to reduce the holding current.

Although the exact degree of current reduction varies depending on the actuator model, load condition, etc.,

the holding current decreases to approx. one-half to one-fourth.

Since the servo remains on, no position deviation occurs.

The actual holding current can be checked in the current monitor screen of the PC software.