IAI America ERC2 User Manual
Page 104
6. Parameter Settings
85
z
Speed loop integral gain (No.32 VLPT)
Parameter No.
Unit
Input range
Default
32
---
1 ~ 217270
Set individually in accordance with the actuator
characteristics.
This parameter is used to determine the response of the speed control loop.
Reducing the set value lowers the response to speed commands, meaning that the reactive force that generates
in response to load change becomes smaller. A smaller set value also results in poorer compliance with position
commands, causing the positioning time to become longer.
If the set value is excessive, on the other hand, the actuator may overshoot or oscillate, rendering the
mechanical parts more prone to vibration.
z
Torque filter time constant (No.33 TRQF)
Parameter No.
Unit
Input range
Default
33
---
1 ~ 2500
Set individually in accordance with the actuator
characteristics.
This parameter determines the filter time constant for torque commands.
If the resonance frequency of the machine is smaller than the response frequency of the servo loop, the motor
vibrates.
This mechanical resonance can be suppressed by increasing the value set in this parameter.
However, increasing the value excessively may reduce the stability of control.
Speed
Set value is large(overshoot)
Set value is small
Time