beautypg.com

IAI America ERC2 User Manual

Page 104

background image

6. Parameter Settings

85

z

Speed loop integral gain (No.32 VLPT)

Parameter No.

Unit

Input range

Default

32

---

1 ~ 217270

Set individually in accordance with the actuator

characteristics.

This parameter is used to determine the response of the speed control loop.

Reducing the set value lowers the response to speed commands, meaning that the reactive force that generates

in response to load change becomes smaller. A smaller set value also results in poorer compliance with position

commands, causing the positioning time to become longer.

If the set value is excessive, on the other hand, the actuator may overshoot or oscillate, rendering the

mechanical parts more prone to vibration.

z

Torque filter time constant (No.33 TRQF)

Parameter No.

Unit

Input range

Default

33

---

1 ~ 2500

Set individually in accordance with the actuator

characteristics.

This parameter determines the filter time constant for torque commands.

If the resonance frequency of the machine is smaller than the response frequency of the servo loop, the motor

vibrates.

This mechanical resonance can be suppressed by increasing the value set in this parameter.

However, increasing the value excessively may reduce the stability of control.

Speed

Set value is large(overshoot)

Set value is small

Time