5. Explanation of Operating Functions

69

Zone signal

Actuator operation

Home

Zone setting-

Zone setting+

+ direction

5.3.9 Zone Signal

This signal is output (the bit turns “1”) when the current actuator position is inside the specified zone. The zone

signal can be used for the following purposes:

[1] As an interlock signal to prevent contact with peripheral equipment

[2] As a trigger signal for peripheral equipment to shorten the tact time

[3] For determining if the actuator has missed the work part during push & hold operation

[4] To determine if the actuator has reached the final point of constant pitch feed over aligned work parts

(Note) In constant pitch feed, the “Position” field of the position table indicates an incremental travel.

However, the zone must be set using absolute coordinates with respect to the home.

Setting

Zone signal

Position number

specification mode

Numerical

specification mode

Individual zone boundaries in the

position table

Position zone output

PZONE

{

x

Zone boundary 1 user parameters

(Parameter Nos. 1 and 2)

Zone output 1

ZONE1

{

{

Zone boundary 2 user parameters

(Parameter Nos. 23 and 24)

Zone output 2

ZONE2

{

{

* The zone signal is output to the zone status register (address 9013H).

When the actuator enters the zone, the bit will turn “1.” The bit remains “0” when the actuator is outside the

zone.

This signal becomes effective after completion of home return. It will remain effective even when the servo is

off, as long as home return has been completed.