IAI America ERC2 User Manual

Page 52

background image

4. W

iring

33

4.1.2 SIO Communication Connection Using a 4-Way Junction

(Note 1) If the total length of the communication cable is 10 m or longer and you experience

communication errors, connect a terminal resistor to the last axis.

(Note 2) If the actuators use different power supplies, align 0 [V] on all power supplies.
(Note 3) The gateway unit power must be the same as 0 V of the ERC2 control power.
(Note 4) Connect the shielded wire of each axis to FG.
(Note 5) If the overall length of link cable exceeds 30 m, use wire of 22AWG or larger size.

Teaching

pendant

Actuator 1

Actuator 2

Actuator 3

Actuator 16

J.S.T.

Mfg.

J.S.T.

Mfg.

24-VDC control power, motor power,

brake signal, ground, shield

e-CON connector

e-CON connector

Fabricated by the customer

Network connection cable

Power & I/O cable

PC, PLC