IAI America ERC2 User Manual
Page 71
![background image](/manuals/350216/71/background.png)
5. Explanation of Operating Functions
52
(Controller o PLC)
Register
Bit
address
Bit
position
Signal
symbol
Signal name
Description
15
to
9
-
-
-
0147H
8
PZONE
Position zone
output
If individual zone boundaries are set in the
position table, this bit will turn “1” when the
current position enters the range specified
by the boundaries.
7
to
2
-
-
-
014EH
1
ZONE2
Zone output 2
This bit will turn “1” when the current
position enters the range specified by the
zone boundary 2 parameters.
Zone status
register
ZONS
Address
9013H
[Common]
014FH
0
ZONE1
Zone output 1
This bit will turn “1” when the current
position enters the range specified by the
zone boundary 1 parameters.
15
to
6
-
-
-
013AH
5
PM32
013BH
4
PM16
013CH
3
PM8
013DH
2
PM4
013EH
1
PM2
Position
number
status
register
POSS
Address
9014H
[POS
specification] 013FH
0
PM1
A completed position number is output
using a 6-bit binary code.
(Controller o PLC)
Register Address
Description
PNOW
Current
position
[Numerical
specification]
The current position is indicated by a signed 32-bit integer (unit: 0.01 mm).
A negative value is indicated by a 2’s complement. Accordingly, the most significant bit
becomes “1.”
Upper
Lower
Sign