7.2 Alarm Level Classification
Alarms output from the controller are classified into two levels according to the symptoms they represent.
Alarm level ALM lamp Failure status
register
What happens when alarm
generates
How to reset
Operation
cancellation
On (Red)
ALMH is “1”
The actuator decelerates to a
stop and then the servo turns
OFF.
x
Perform an alarm reset
from a PC/teaching
pendant.
x
Input a RES signal from
the PLC.
Cold start
On (Red)
ALMH is “1”
The actuator decelerates to a
stop and then the servo turns
OFF.
x
Perform a software reset
from a PC/teaching
pendant.
x
Reconnect the power.
7.2.1 How to Reset Alarms
Enter the alarm reset input signal (RES).
After the ALMH signal bit has returned to “0,” confirm that the ALMH bit is “0,” and then change the RES signal
bit to “0.”
Caution: Before resetting an alarm, always identify and remove the cause of the alarm.
If the cause cannot be removed or the alarm still persists after removing the cause,
contact IAI.
If the same error occurs again after resetting the alarm, the problem that caused the alarm
in the first place is still present.
Alarm reset input signal (RES)
Alarm output signal (ALMH)
Alarm present
Alarm reset