Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual
Page 90
Logic Functions - Book 1
LOOP BLOCK
4-8
Table 4-1. ICN Communication Block Attributes, Valid Values, Mnemonics, and Data Types (Cont’d)
Field Name /
Attribute
Mnemonic
Valid Values
CWR
Data Type
Attr
Bus Restart Counter
RSTC
– WR
Count
34
Restart Failure Counter
FAILC
– WR
Count
35
Invalid Message Counter
MSGC
– WR
Count
36
Check-Sum Error Counter
CRCC
– WR
Count
37
Framing Error Counter
FRAMEC
– WR
Count
38
Noise Error Counter
NOISEC
– WR
Count
39
Overrun Error Counter
ORUNC
– WR
Count
40
Invalid msg. Length Counter
LENC
– WR
Count
41
Receive Buffer Full Counter
RFULLC
– WR
Count
42
Xmit. Buffer Full Counter
XFULLC
– WR
Count
43
Unexp. Comm. Msg. Counter
UCOMMC
– WR
Count
44
ICN Overload Counter
OLOADC
– WR
Count
45
Req. Buffer Full Counter
QFULLC
– WR
Count
46
Foreground List
FG
NONE(0), CL10(10) to CLn
CWR
Count
47
ICN Load
LOAD
– – R
Msec Time
48
Reset Diagnostic Ctrs
RESET
NO (0), YES (1)
– WR
Discrete
49
I/O Module Mismatch
MODMM
NO (0), YES (1)
– – R
Discrete
51
ICN Address
ADDR
ANY, 0 to 15
– – R
Short State
52
Board number
BOARD
1
– – R
Long State
53
Slot number
SLOT
32, 30, 29, 28, 27, 26
– – R
Long State
54
Terminating Source
TERM
FALSE (0), TRUE (1)
– – R
Discrete
55
02
State (STATE) .................................................................................................................... – – R
Not configurable in this block (always equal to RUN). See Section 2.4.1, State Changes for
additional information. This block, when configured, is always executed in the RUN state
(Normal Operation).
03
Bad Inputs Accepted (BADINP) ....................................................................................... – – R
This attribute is not used with this block. The ICN communication block always runs without a
check on input quality. See Section 2.3.2, Data Quality for additional information.
04
Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.
NONE
No group assigned.
1 to 7
The number of the diagnostic suppression group as controlled by the System
Event block.