beautypg.com

Diagnostic attributes – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 37

background image

Logic Functions - Book 1

INTERFACE BLOCK

3-11

Table 3-1. Interface Block Attributes, Valid Values, Mnemonics, and Data Types (Cont’d)

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Scan1 Max. Execution Time

MTIME1

Maximum Scan Msec Time

– WR

Msec Time

186

Scan2 Max. Execution Time

MTIME2

Maximum Scan Msec Time

– WR

Msec Time

187

Scan3 Max. Execution Time

MTIME3

Maximum Scan Msec Time

– WR

Msec Time

188

Scan4 Max. Execution Time

MTIME4

Maximum Scan Msec Time

– WR

Msec Time

189

Scan5 Max. Execution Time

MTIME5

Maximum Scan Msec Time

– WR

Msec Time

190

Scan6 Max. Execution Time

MTIME6

Maximum Scan Msec Time

– WR

Msec Time

191

Scan7 Max. Execution Time

MTIME7

Maximum Scan Msec Time

– WR

Msec Time

192

Scan8 Max. Execution Time

MTIME8

Maximum Scan Msec Time

– WR

Msec Time

193

Scan9 Max. Execution Time

MTIME9

Maximum Scan Msec Time

– WR

Msec Time

194

lock I/O blocks?

IOLOCK

NO (0), YES (1)

CWR

Discrete

195

Run completion cycles

RCCYCLES

1 to 255

CWR

Long State

196

Run complete input

RUNCMPLT

NONE, TRUE, FALSE, LSP

CWR

Discrete

197

3

Bad Inputs (BADINP) .........................................................................................................CWR
See Section 2.3.2, Data Quality for additional information.

ACCEPTED

1

Block runs without a check on input quality.

REJECTED

0

The only input, Run Complete, is treated as FALSE when the input
quality is BAD.

Diagnostic Attributes

4

Default Database Checksum Error Unacknowledged (DEFCKUAK)............................ – WR
The unacknowledged default database checksum error diagnostic indicates if the error is or is
not acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

5

Default Database Checksum Error Active (DEFCKACT)................................................– – R

The instrument was shut down due to a checksum error in the default database.

YES

1

“DEFAULT DATABASE CHECKSUM ERROR” is active.

NO

0

Diagnostic error is not active.

6

Main Database Checksum Error Unacknowledged (MNCKUAK) ................................. – WR
The unacknowledged main database checksum error diagnostic indicates if the error is or is
not acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

7

Main Database Checksum Error Active (MNCKACT) .....................................................– – R
The instrument was shut down due to a checksum error in the main database.

YES

1

“MAIN DATABASE CHECKSUM ERROR” is active.

NO

0

Diagnostic error is not active.