Report Process Alarm Events (RPTPA) ....................................................................CWR
Used to enable reporting of Process Alarm events.
YES
1
Report process alarm events to the event queue.
NO
0
No event reporting is made for ALL Process Alarms in the
database.
38
Report Notification Message Events (RPTNM) ........................................................CWR
Used to enable reporting of notification/request message events.
YES
1
Report notification/request message events to the event queue.
NO
0
No event reporting is made for ALL Notification/Request
Messages in the database.
39
Report System Event Events (RPTSE)......................................................................CWR
Used to enable reporting of system events.
YES
1
Report this block’s events to the event queue.
NO
0
No event reporting is made for the System Event block.
40
Global Acknowledge Command (GLBACK) ............................................................. – WR
Writing TRUE to this command causes all diagnostics, process alarms and notification/
request messages to be acknowledged. This is a one shot type command (value in
database remains FALSE).
41
Diagnostic Acknowledge Command (DGACK) ....................................................... – WR
Writing TRUE to this command causes all diagnostic alarms to be acknowledged. This is
a one shot type command (value in database remains FALSE).
42
Process Alarm Acknowledge Command (PAACK) ................................................. – WR
Writing TRUE to this command causes all process alarms to be acknowledged. This is a
one shot type command (value in database remains FALSE).
43
Notification/Request Message Acknowledge Command (NMACK) ...................... – WR
Writing TRUE to this command causes all notification/request messages to be
acknowledged. This is a one shot type command (value in database remains FALSE).
44
Clear Queue Command (CLRQCMD)........................................................................ – WR
Writing TRUE to this command causes the event queue to clear. This is a one shot type
command (value in database remains FALSE).
45
Any Active Diagnostics (ANYACT) ............................................................................– – R
The active diagnostics status output is a block output that is TRUE when there is any
active diagnostic alarm in the instrument; otherwise, it is FALSE (no active diagnostic
error).
46
Any Unacknowledged Diagnostics (ANYUNK).........................................................– – R
The unacknowledged diagnostic status output is a block output that is TRUE when there
is any unacknowledged diagnostic alarm in the instrument; otherwise, it is FALSE (no
unacknowledged diagnostics).